Audio Amplifiers; 60/120 Watt Amplifier Module - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

The OWS is supplied with a wide range of high efficiency class-D audio amplifiers: 60, 120
or 250 Watts. A basic OWS system fitted in FT1020G3 supports the following standard
Features:
Digital voice messages for alert and T3 (or AS2220 evacuation tone)
Supervised trigger Input (short/open circuit fault)
Supervised dual Strobe 24V
Supervised 100V speaker line output (open/short circuit fault).
Fault Relay output (changeover contacts)
Fault indicators for strobe output, trigger input and speaker circuit on OWS main
board. Only one common fault indicator on the front display.
Built in electret microphone.
Auxiliary input to connect to Brooks single or multiple zone remote microphones
Auxiliary audio enable/disable switch input.
An optional expansion 4 zone splitter board can be fitted with the standard OWS, maximum
of 4 boards can be used to provide up to 16 fully supervised speaker zone circuits.
The four zone splitter boards can be used to individually select one of the four zones (or all
zones) for PA announcement purposes only
zones and requires 2 x 4 zone splitter board.
6.4.2

Audio Amplifiers

60 Watt audio amplifier SUB865
120 Watt audio amplifier SUB866
250 Watt audio amplifier SUB867
Standard 60W OWS can be powered from the FT1020G3 power supply (battery backup
must be upgraded). When larger OWS is required e.g. 120W or 250W, separate power
supply and power supply supervision must be used. Larger amplifiers may require larger
cabinets depending on the space available.
6.4.2.1

60/120 Watt Amplifier Module

Features:
High energy efficiency class D amplifier design.
Available in 60W and 120W configuration.
Standby function to reduce power consumption.
Designed to mount on top of the main control OWS module to save space
39
In NZ applications, the OWS has to be configured to provide AS2220 tones and voice messages.
40
OWS faults are hardwired via this common fault relay to input I0 - 13 in FT1020G3 to display OWS fault on the LCD. In NZ
convention, I0 cannot be used, it has to be I1 - !3.
41
The tone / message is common for all zones, only PA can select one or multiple zones for announcement.
Technical/Programming Manual
output for alert and evacuation strobes.
DC
40
41
. The PA front display can select up to 8 PA
42
FT1020G3 Rev 2.2.1