The AAF zone xx (xx=00-99) is only valid for the CIE it is shown in, i.e. not for the whole
system.
Notes:
The AAF alarm indication is only shown in one Control Unit, i.e. in the Control Unit
to which the AAF equipment is connected.
All devices within the same AAF zone must be connected to the same CIE
Maximum number of smoke detectors in an AAF zone is 5.
Smoke detectors in an AAF zone cannot be programmed as 2-unit-dependent and
not be controlled by the Alert Annunciation function.
Only Analogue photo electric smoke detector 4401 (4301) and Analogue multi
detector 4400 (4300) can be used for AAF. If the Analogue multi detector 4400 is
used, it must be programmed as type "Two addresses", so that only the "smoke
part" of the detector can be used in AAF function.
Max. 100 AAF zones (00-99) per CIE
The sounder base 3379 has to be programmed with the trigger condition "AAF
zone alarm" (and other trigger conditions).
17.13.2

Local Alarm Acknowledgement (LAA)

The local alarm acknowledgement is the European's equivalent of the Australian alarm
acknowledgement facility. The function is identical to the AAF explained in section 17.13.1
with different terminologies. The functionality of Panasonic's LAAU and Brooks AAM are
shown in Table 13 below.

Table 13 Alarm acknowledgement function

Product code
Module's name
Function's name
Trigger type in EBLWin
No. of zones
No. of detectors per
zone
Acknowledgement
period
Investigation period
Sounder unit
Ack. Message on LCD
Investigation message
on LCD
One LAA zone consists of one to five analogue smoke detectors 4400 / 4401 (4300 / 4301),
one LAA buzzer (sounder base 3379) and one Local Alarm Acknowledgement Unit (LAAU).
All connected on the same COM loop.
Note: All devices included in an LAA zone must be connected to the same CIE.
The local alarm acknowledgement connection diagram is shown in Figure 44 below.
Panasonic LAAU
4445
Local Alarm Acknowledgement
Unit LAAU
Local Alarm Acknowledgement
LAA
LAA
Max. 100 LAA zone
5 x 4400/4401 (4300/4301)
10-120 seconds
1-9 minutes
3379
LAA zone xx, activated
LAA zone xx, investigation in
progress
117
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Brooks AAM
3340
Alarm Acknowledgement
Module AAM
Alarm Acknowledgement
Facility AAF
AAFC
Max. 100 AAFC zone
5 x 4400/4401 (4300/4301)
10-120 seconds
1-9 minutes
3379
AAF zone xx, activated
AAF zone xx, investigation
in progress