Alarm Acknowledgement Facility (Aaf) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.10
The Acknowledge time can be set to 5-60 seconds.
The Investigation time can be set to 1-9 minutes.
NOTE! According to EN54-2, the total delay of fire alarm routing
equipment must not exceed 10 minutes (i.e. Acknowledge time +
Investigation time < 10 min.).

Alarm Acknowledgement Facility (AAF)

This function is similar to the "Alert Annunciation Function"
(described above) and used on the Australian market only.
One AAF zone can be one to five analog smoke detectors (4300 /
4301), one AAF buzzer (e.g. Sounder base 3378) and one AAF
102
Control (AAFC)
. All connected on the COM loop.
COM loop
Sounder Base 3378
AAF
PRESS TO ACKNOWLEDGE
FALSE ALARM
Figure 21. Alarm Acknowledgement Facility units.
Function (see also the flow chart in the following figure):
- One of the detectors in an AAF zone reaches its fire alarm level.
The AA Process starts and the AAF buzzer sounds.
- An Acknowledgement Period starts
(AP=10-60 sec. -- programmable).
- If it is a false alarm, acknowledge the alarm on the AAFC before
the AP is ended.
- After acknowledgement an Investigation Period starts and the AAF
buzzer is silent
(IP=0-3 min. -- programmable).
If all the detectors in the AAF zone becomes normal again (i.e. goes
below the fire alarm level respectively) during the IP, the AAP ends.
If the AP or the IP runs out during the AAP and any detector in the
AAF zone still is over its fire alarm level, normal fire alarm(s) will be
activated.
102
This unit is available on the Australian market only.
EBL128 Planning Instructions V1.1.x
Smoke detector (4300, 4301)
AAFC
LED
Non-latching switch
93