Battery Faults; Fault: Battery; Fault: Low Battery Capacity - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
14.1.2.1
14.2
14.2.1
14.2.2
The outside switch is turned OFF (i.e. from activated to not
activated state).
 The fault "
FAULT: FB Silence switch active"
124
Serviced
.
 Any fire alarm ("ALM") and acknowledged alarm ("ACK") will
automatically be disabled / isolated. (I.e. it has to be re-
enabled via menu H2/B5-B6.)
"Disablements".
 Any fire alarm ("ALM") and acknowledged alarm ("ACK") will
automatically change the state to "Isolated alarm" (see below)
and in the fire alarm list (presented in the LCD) "
ACK
"
" will be replaced with "
An example:
ISO ZONE-ADDR 12-46 LAST ZONE 12
This is a user defined alarm text.
Isolated alarm
A fire alarm will automatically change state to "Isolated alarm" when
the "outside switch" (see above) is turned OFF, i.e. when it is not
activated any more (see above).
The following is valid for an isolated alarm.
 LED:s "Fire" (on the front) will not be activated.
 The c.i.e. built-in buzzer will not be activated.
 Presented as isolated alarm, see the example above (ISO ......).
 Programmable outputs will not be activated.
 Output for routing equipment (Fire brigade tx) will not be
activated.

Battery faults

For other conventions, see chapter "Security functions", page 138.

FAULT: Battery

The following battery check is performed:
 The battery charging is turned off every 30
 Battery voltage is checked.
 Battery voltage < 24.4 V generates a fault.
Fault message:

FAULT: Low battery capacity

The following battery check is performed:
124
Since this fault is always latched, it has to be acknowledged via menu H6.
107
EBL128 Planning Instructions V1.1.x
ISO
".
FAULT: Battery
will be
Indicated by LED
ALM
" or
No. 01
th
second.