Programmable Outputs - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
9

Programmable outputs

EBL128 has two programmable voltage outputs (S0 and S1) and one
programmable relay output (R0). 8 relay outputs expansion board
4581 can be mounted in EBL128. Input and Output expansion board
4583 with three programmable outputs (Output 0-2) can be mounted
in EBL128. See chapter "Expansion boards 458x", page 22.
On the COM loop can be connected Addressable Multipurpose I/O
unit 3361 with two programmable relay outputs (Re0 and Re1) per
unit and Addressable 2 voltage outputs unit 3364 with two
programmable voltage outputs (VO0 and VO1) per unit. Addressable
siren 3377 and Addressable sounder base 3378 can also be connected
on the COM loop, i.e. these units have no physical output, only the
siren and sounder respectively.
NOTE! Units type 3361 + 3364 = max. 16.
Units type 3377 + 3378 = max. 50.
Each output is programmed (via Win128), when applicable, regarding:
Name (Normally not changed)
Type
Output signal period (continuous, pulse, delay, etc.)
Logic (NO / normally low or NC / normally high)
Supervised / Not Supervised (The EBL128 voltage outputs, Input
and Output expansion board 4583 voltage outputs (Output 0-1)
and Addressable 2 voltage outputs unit 3364.)
Control expression (with one or more trigger conditions).
If Enter arguments in dialog is selected a separate dialog box is
opened for easier entering of the required data (e.g. zone, address,
etc.). Current size gives a rough indication of how big the
control expression is.
depending on the number and types of trigger conditions but also
the logical operators used in the control expression.
Figure 11.
The Win128 dialog boxes "Voltage" & "Relay
Output" respectively.
EBL128 Planning Instructions V1.1.x
Normally it should be < 80 but it is
60

Advertisement

Table of Contents
loading

Table of Contents