Control Unit Outputs S0 - S1 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
9.1
Each 3377 and 3378 unit is programmed (Win128) regarding:
Technical address
Name (Normally not changed)
Priority level (High / Low)
For each priority level:
 Sound
type
(Steady/continuous,
Alternating/two-tone)
 Name
 Type (Normally "Alarm device")
 Output signal period (Normally "Steady")
 Control expression (with one or more trigger conditions)
If Enter arguments in dialog is selected a separate dialog box
is opened for easier entering of the required data (e.g. zone,
address, etc.). Current size gives a rough indication of how
big the control expression is. Normally it should be < 80 but it
is depending on the number and types of trigger conditions but
also the logical operators used in the control expression.
Figure 12. The Win128 dialog box "Addressable siren 3377"
(The dialog box "Addressable sounder base 3378" is similar).
Control unit outputs S0 – S1
EBL128 has two programmable, supervised (monitored)
outputs:
59
Supervised as default but via Win128 it is possible to set each output
individually as not supervised (not monitored). A normally high output can
not be supervised.
Supervised outputs have to be calibrated via menu H5/A3, see the EBL128
Operating Instructions. 1-5 supervision resistors 33K can be used. The
calibrated value has to be in the range 4K7-50K. A fault will be generated
EBL128 Planning Instructions V1.1.x
Intermittent/pulsed
61
or
59
voltage