Output Signal Periods

Figure 31. The Win128 tab page "Control Unit Properties" with
the tab "Output Signal Periods" open.
See also chapter "Output signal period", page 66.
In the list (to the left), Steady (continuously) and Intermittent 0.8 /
0.8 s are already defined since these alternatives are often used. It is
however, possible to define them to something else.
User defined 1-8 have to be defined individually:
Name: Normally changed to something that describes the output
signal (e.g. "Steady") or what it is meant for (e.g. "Alarm devices").
Type: Steady / continuous (default)
130
Intermittent
Pulse
Steady, delayed activation
Intermittent, delayed activation
Pulse, delayed activation
Steady, delayed de-activation.
Depending on the selected type, one or more of the following fields
might have to be filled-in.
Delay time: Can be set to 0-255 sec.
Pulse length: Can be set to 0-255 sec.
Pulse off: Can be set to 0-255 sec.
De-activation: Can be set to 0-255 sec.
130
NOTE! The Pulse length and the Pulse off times both have to be the
same, e.g. 0.8 and 0.8 sec.