Input Programming; Type (Trigger Conditions) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
8
8.1

Input programming

Input programming is done via Win128. For more information, see
the Win128 help.
Each input has to have an individual Trigger
condition ("Type") and Logic. Each input can be supervised or not
supervised. It is not recommended to let two or more inputs have the
same trigger condition.

Type (trigger conditions)

The following trigger conditions are available:
1. Not used
2. Alarm Key Cabinet (one input)
3. Alert Annunciation Acknowledge
4. Alert Annunciation Reset
5. Fault Signal External Power Supply (one input)
6. Fault Signal External Fuses (one input)
7. External Time Channel 5 - 12 (one input per time channel)
8. General Fire (max. 127)
9. Activated Routing Equipment (one input)
10. External Fault
11. Interlocking (max. 32 inputs)
12. Loss of main power source to external power supply (one
input)
13. Loss of battery charger to external power supply (one input)
14. Door Closing Test Input
15. Pre-warning
16. Activated fault routing equipment (one input)
17. Extinguishing system released
18. Extinguishing system fault
19. Extinguishing alarm
20. Fault warning routing equipment fault
21. Activate output
22. Silence alarms (one input)
23. Activated key cabinet
24. Evacuate
57
25. Zone Line Input
Comments to the trigger conditions:
57
Only valid for the Addressable multipurpose I/O unit 3361 input "In0",
used as zone line input (Z).
EBL128 Planning Instructions V1.1.x
56