Fire Door Closing function

85
Programmable outputs
trigger condition is available (no. 34 = Fire Door Closing). Type of
output shall normally be "Control, neutral". One or more alarm points
can control the output, e.g. the detectors on both sides of the fire door.
S
01-01
Fire Door Closing function (ABDL)
In case of one of the following events, the output will be "activated"
(i.e. powerless) and the fire door will close:
 Fire alarm (any of the programmed detectors)
 Fire alarm in "Test mode" (any of the programmed
detectors)
 Fault (i.e. "no answer" from any of the programmed
86
detectors
)
 Disablement (any of the programmed detectors, the involved
zone(s) or the COM loop).
 A definite time every day, if programmed via Win128. (The
output will be activated for 20 seconds.)
 Via a programmable input (trigger condition no. 17 = Door
Closing Test Input). (The output will be activated for 20
seconds.)
NOTE!
For safety reasons should an I/O unit 3361 output not be used.
there is a short-circuit or a double break on the COM loop, the I/O
unit can not be "ordered" to activate the output, i.e. the door will not
be closed.
If a magnet contact is available, it is possible to get a "closed fire door
verification" via the Interlocking function. In this case, Type of in-
/output has to be "Interlocking in-/output".
"Interlocking function", page 76.
85
In the DBI (Danish) convention, must only EBL128 outputs R0 and S0-S1
as well as the 3364 unit be used and "Type of output" has to be "Control
neutral".
86
E.g. a faulty detector, two breaks or short-circuit on the COM loop.
EBL128 Planning Instructions V1.1.x
can be used for fire door closing. A special
Fire
door
M
Door release magnet
Programmable output
79
Smoke detector
S
01-02
85
If
See also chapter