Current Consumption - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
COM loop units (input units)
Analog heat detector 3308 + analog base 3312/4313
Analog heat detector, enclosed 3309
Analog multi detector 4300 + analog base 3312/4313
Analog smoke detector 4301 + analog base 3312/4313
Addressable manual call point 3333 / 3339
Addressable Base station for wireless units 4610
NOTE! Regarding the COM loop units: Max. 5 internal LEDs will be turned on even if more
alarm points are activated. (I.e. also max. 5 external LEDs will be turned on.)
COM loop units (output units / other units)
Addressable siren 3377
Addressable sounder base 3378 (low/high)
Addressable sounder base 3379
Addressable multipurpose I/O unit 3361
Addressable 2 voltage outputs unit 3364
Analog base with isolator 4313
Addressable short circuit isolator 4370
(Addressable) External power supply 3366
I/O Matrix board
Alarm Acknowledge Facility Control (AAFC)
Rev: 3
138
Extern LED current consumption. 2218: 2 mA; 2217: 1 mA.
139
External 24 V DC power supply also required (via a 3366 unit or
EBL128).
140
Detector not included.
141
This unit is available on the Australian market only.
EBL128 Planning Instructions V1.1.x
Normal state (mA)
138
0.3
138
0.2
138
0.3
138
0.3
2
139
1.5
Normal state
(quiescent) (mA)
1
2
0.75
2.2
139,
< 6
140
< 1.3
2.2
< 15
141
max. 6
141
2
133
Alarm state
(activated) (mA)
0.3 + 2
(int. LED)
0.2 + 1.5
(int. LED)
0.3 + 2
(int. LED)
0.3 + 2
(int. LED)
2 + 3
(int. LED)
2.2
Alarm state
(activated) (mA)
max. 13
max. 6 / 12
max 3
max. 12
< 6
< 1.3
2.2
< 15
max. 6
5