Logical Operators; Control Expression Examples - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
10.5.2
10.5.3
34
This trigger condition plus the OR operator shall be used
for each detector (zone-address) controlling a fire door
(normally > two detectors). Type of output is normally
"Control, neutral".
function", page 80.
35
Service signal is activated (by any sensor).
36
Used for routing equipment (Fire brigade tx) output only.
Has to be type Routing Equipment (Fire brigade tx).
NOTE! The Alert Annunciation function is working
with this trigger cond. (If this function shall not be used,
use trigger cond. "General fire alarm" instead.)
37
"Alarm Acknowledgement Facility" alarm activated in
the specified AAF Zone. Required "AAF Control" unit is
available on the Australian market only.
38
Any "Quiet alarm" in the specified zone will activate the
output. Used e.g. for the Australian fan control function.
39
One specified "Quiet alarm" in the specified zone will
activate the output. Used e.g. for the Australian fan
control function.
40
Output
activated
"Extinguishing system fault" is true.
41
Output
activated
"Extinguishing system released" is true.
42
Output activated when input trigger condition "Activated
key cabinet" is true.
43
Output activated when input trigger condition "Multiple
detector alarm" is true, i.e. fire alarm type A.
44
Output activated when input trigger condition "One
detector alarm" is true, i.e. fire alarm type B.

Logical operators

The logical operators available in Win128 are in priority order:
( )
parentheses, changes priority order
NOT
not-function (inverts), is written NOT in Win128
AND
and-function, is written AND in Win128
OR
or-function, is written OR in Win128

Control expression examples

In order to understand the possibilities to create control expressions,
here follow some AND, OR, NOT and ( ) examples and also some
control expression examples.
76
Indicated by LED "Fault / Disablements Alarm devices".
77
In Danish convention (DBI), must only EBL128 outputs R0, S0-S1 and
the COM loop unit 3364 be used. The type has to be "control neutral".
78
Indicated by LED "Service".
79
See chapter "Fire alarm type A and Fire alarm type B", page 96.
EBL128 Planning Instructions V1.1.x
77
See also chapter "Fire Door Closing
when
input
when
input
71
78
trigger
condition
trigger
condition
79
79