Dell External M1000e t Owner's Manual page 75

Owners manual
Table of Contents

Advertisement

CAUTION: When installing the unit, the ground connection must always be made first and disconnected last to
prevent an energy hazard.
CAUTION: Never defeat the ground conductor or operate the equipment in the absence of a suitably installed
ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that
suitable grounding is available.
Input Requirements
Supply voltage: –(48–60) V DC
Current consumption: 75 A (maximum)
Kit Contents
Molex # 394260002 at PSU end
Molex # 39422-0012 mating DC power connector
Required Tools
Hand-crimping tool (Tyco Electronics 1490749-1, Upper Die 1490414-2, Lower Die 1-1490413-6).
Wire-stripper pliers capable of removing insulation from size 4 AWG solid or stranded, insulated copper wire.
NOTE: Use alpha wire part number 3080 or equivalent (65/30 stranding).
Required Wires
One UL 4 AWG, 2 m maximum (stranded) black wire [–(48–60) V DC]
One UL 4 AWG, 2 m maximum (stranded) red wire (V DC return)
One UL 4 AWG, 2 m maximum (stranded) green/yellow/green with a yellow stripe wire (safety ground)
Assembling And Connecting The Safety Ground Wire
WARNING: For equipment using –(48–60) V DC power supplies, a qualified electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All
electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that
is not authorized by Dell is not covered by your warranty. Read and follow all safety instructions that came with the
product.
1.
Strip the insulation from the end of the green/yellow wire (safety ground wire), exposing approximately 4.5 mm
(0.175 inch) of copper wire.
2.
Using a hand-crimping tool (Tyco Electronics 1490749-1, Upper Die 1490414-2, and Lower Die 1-1490413-6), crimp
the ring-tongue terminal (Amp/Tyco PN 33115-1) to the green/yellow wire.
3.
Connect the safety ground wire to the grounding post on the back of the system using a #5/16 nut equipped with a
locking washer.
The nut must be torqued to 16 in lbs (1.8 N-m) to ensure proper ground wire retention.
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Poweredge m1000e

Table of Contents