INSTALLATION

4.4 Ventilation

When installing TMS7 starters in an enclosure there must be
sufficient air flow through the enclosure to limit heat rise within
the enclosure. Temperature within the enclosure must be kept
at, or below, the TMS7 maximum ambient temperature rating.
If installing an TMS7 within a totally sealed enclosure a bypass
contactor must be employed to eliminate heat dissipation from
the soft starter during run.
Soft starters dissipate approximately 4.5 watts per amp. The
table below shows air flow requirements for selected motor
currents. If other heat sources are installed in an enclosure
along with the TMS7 an additional air flow allowance must be
made for these items. Note that heat generation from
semiconductor fuses, if used, can be eliminated by installing
these within the bypass loop.
Motor
Heat
Amps
(watts)
5
Rise
10
45
20
90
30
135
40
180
50
225
75
338
100
450
125
563
150
675
175
788
200
900
250
1125
11.3
300
1350
13.5
350
1575
15.8
400
1800
18.0
450
2025
20.3
500
2250
22.5
550
2475
24.8
600
2700
27.0
10
Required Airflow
m
/min
m
/hour
3
3
C
10
C
5
C
10
C
o
o
o
o
Rise
Rise
Rise
0.5
0.2
30
15
0.9
0.5
54
27
1.4
0.7
84
42
1.8
0.9
108
54
2.3
1.1
138
69
3.4
1.7
204
102
4.5
2.3
270
135
5.6
2.8
336
168
6.8
3.4
408
204
7.9
3.9
474
237
9.0
4.5
540
270
5.6
678
339
6.8
810
405
7.9
948
474
9.0
1080 540
10.1
1218 609
11.3
1350 675
12.4
1488 744
13.5
1620 810
ME00070B
TMS7 SERIES