8.3 Soft Braking

3 PHASE
SUPPLY
CO NTR OL
SUPPLY
F1
L1
L 2
L3
A1
A2
CONTROL
SUPPLY
FLC SELECT
T3
T1
T2
E
I44
I 43
K3 A
K2M
K1 M
CO NTACTORS TO BE
MECHANICAL LY
INTERL OCKED
M1
Description:
For high inertia loads that require more braking torque than is available from the D.C.Brake feature, the TMS7 can be configured for 'Soft
Braking'.
In this application the TMS7 is employed with forward run and braking contactors. On receipt of a start signal (pushbutton S1) the TMS7
closes the forward run contactor (K1M) and controls the motor according to the programmed Primary Motor Settings.
On receipt of a stop signal (pushbutton S2) the TMS7 opens the forward run contactor (K1M) and closes the braking contactor (K2M) after a
delay of approximately 2-3 seconds (K1T). K3A is also closed to activate the Secondary Motor Settings which should be user programmed
for the desired stopping performance characteristics.
When motor speed approaches zero the shaft rotation sensor (A2) stops the soft starter and opens the braking contactor (K2M).
Function Settings:
Function 23. Relay Output C Functionality = 0 (Assigns the Trip function to Relay Output C)
-
Functions 1~9 (Sets starting performance characteristics)
-
Functions 80~88 (Sets braking performance characteristics)
-
TMS7 SERIES
THERMISTO R
IN PUT
A3
C1
C2
R11
THERMISTO R
IN PUT
RELAY
OUTPUT C
START
STO P
RESET
I34
I33
I2 2
I 21
I12
I11
R12
K2A
S3
K1 A
K3A
S2
K2T
K1T
S1
K1 A
K1 M
K2M
K1A
LEG EN D
A2
SHAFT RO TATION SEN SO R
F1
SEMI -CO NDUCTOR FUSES ( OPTION AL)
K1 A
RUN RELAY
K2 A
START RELAY
K3 A
BRAKE RELAY
K4 A
ROTATIO N SENSING REL AY
K4 A
A2
K1M K2M
K1A
K1T
K1 M
Y1
K2M
Y1
Y2
Y2
K2A
K3A
K4 A
K1M
LINE CONTACTO R ( RUN)
K2M
LINE CONTACTO R ( BR AKE)
K1T
RUN DEL AY TIMER
K2T
BR AKE DELAY TI MER
S1
START PUSHBUTTO N
S2
STOP PU SHBUTTON
S3
RESET PUSHBU TTON
ME00070B
APPLICATION EXAMPLES
CON TRO L
SUPPLY
K2 T
27