ICP-CC404 | Installation Guide | 16.0
Table 50:
Test Reporting Time Parameters
Location
Parameter
360
Hour of day (tens digit)
361
Hour of day (units digit)
362
Minute of day (tens digit)
363
Minute of day (units digit)
364
Test Report (tens digit)
365
Test Report (units digit)
366
Repeat interval in days
A Test Report (Contact ID Event Code 602) is a
specific signal sent to the base station receiver and is
normally used to test the dailing and reporting
functions of the control panel.
When programming Test Report options, specify the
hour and minute of the day the report is required,
and how often to send the report. Test reports are
sent on a daily basis from every day to every fifteen
days. Refer to Section 6.1.1 Set the Number of Days until
the First Test Report on page 27 to set the first test
report.
If Test Reports are not required, program
the repeat interval in Location 366 as 0.
Program the Test Report Time as 24:00
to send reports every 30 min.
Example
To send Test Reports once every seven days at 11:35
PM, program Locations 360 to 366 as:
2 3 3 5 7 1 7

15.22 Test Reporting Dialer Options

Use Location 367 to select whether Test Reports are
sent to Receiver 1 (the default), Receiver 2, or both,
Receiver 2 only when Receiver 1 fails, or there is no
reporting at all. Table 51 lists the reporting options.
Table 53:
Output Programming Defaults
Output
Default Output Type
Output 1
Horn Speaker
Output 2
Fire Alarm with Verification
Strobe
Strobe – Reset in 8 hr
Relay
Sirens Running
Codepad
Entry/Exit Warning and
Buzzer
Day Alarm
16.1
Redirecting Outputs to the Codepad
Buzzer
Multiple output event types can be directed to the
codepad buzzer so the buzzer can indicate a number
of events.
64

Programmable Outputs

Table 51:
Default
Option
0
0
0
1
0
2
0
4
7
8
1
16.0 Programmable Outputs
0
The ICP-CC404 Control Panel has four fully-
programmable outputs on the main printed circuit
board and one programmable output that operates
the codepad buzzer. The four outputs are set by
default to operate as horn speaker, fire alarm
verification, strobe, and internal screamer.
Programmable outputs require four parameters to
operate correctly.
Table 52:
Parameter
Event Type
Polarity
Time Base/
Time
Multiplier
Locations
Event Code
368 to 373
1
14
374 to 379
2
7
380 to 385
2
0
386 to 391
1
15
392 to 397
0
13
To redirect an output to the codepad buzzer, select an
output and program it for the desired Output Event
Type. If the output is functioning correctly, add 8 to
the first (tens) digit of the Output Event Type.
Bosch Security Systems, Inc. | 12/08 | F01U089401-02
Test Reporting Options
Description
No Test Reports required
Receiver 1
Receiver 2
Receiver 1 and Receiver 2
Receiver 2 only when Receiver 1 fails
Outputs 1 to 4 do not operate when the
control panel detects a low battery.
Output Parameters
Description
The Event Type specifies when an output
is activated. The Output Event Types are
listed in Section 16.2. Enter the code for
the Output Event Type into the two
corresponding locations for the output.
Polarity determines whether the output
operates for the duration of the event,
pulses for the duration, operates once only
(one shot), or latches on. The polarity
options are listed in Table 54 on page 69.
The Time Base and Time Multiplier
parameters determine how long and how
often the output operates. Refer to Section
16.4 Output Timing on page 70.
Polarity
Time Base
Time Base Multiplier
0
0
0
10
2
1
6
4
0
1
0
0
2
1
0
0
5
8
0
1