Entry Timer 2; Exit Time; Entry Guard Timer For Stay Mode; Delay Alarm Reporting Time - Bosch ICP-CC404 Installation Manual

Hide thumbs Also See for ICP-CC404:
Table of Contents

Advertisement

You can program Entry Timer 1 from 0 to 255 sec in
increments of 1 sec. Entry Timer 1 is the delay time
used by the Delay-1 Zones. Refer to Section 14.3.1
Zone Types on page 55 for more information.
17.3

Entry Timer 2

Program Entry Timer 1 into Locations 400
(increments of 1 sec) and 401 (increments of 16 sec).
The default value for Entry Timer 2 is 40 sec (8 2).
You can program Entry Timer 2 from 0 to 255 sec in
increments of 1 sec. Entry Timer 2 is the delay time
used by Delay-2 Zones. Refer to Section 14.3.1 Zone
Types on page 55 for more information.
17.4

Exit Time

Program Exit Timer into Locations 402 (increments
of 1 sec) and 403 (increments of 16 sec).
The default value for the Exit Timer is 60 sec (12 3).
You can program the Exit Timer from 0 to 255 sec in
increments of 1 sec. When arming the system in
AWAY Mode, the remote codepad beeps during Exit
Time until the final 10 sec, when the codepad sounds
one continuous beep to indicate the end of Exit Time
is near.
The remote codepad always sounds one short beep at
the end of Exit Time when arming in STAY Mode 1
or STAY Mode 2.
17.5

Entry Guard Timer for STAY Mode

Program Entry Guard Timer for STAY Mode into
Locations 404 (increments of 1 sec) and 405
(increments of 16 sec).
The default value for Entry Guard Timer for STAY
Mode is 0.
Entry Guard Timer for STAY Mode is the delay time
used for all zones except 24-Hour Burglary and 24-
Hour Fire Zones when the system is armed in STAY
Mode 1 or STAY Mode 2. All zones, including Delay
Zones, use this timer for the entry delay (for example,
the Entry Guard Timer overrides the delay time
programmed for a Delay Zone). If the Entry Guard
Timer is programmed as 0, each zone acts according
to its programmed zone type.
17.6

Delay Alarm Reporting Time

Program the Delay Alarm Reporting Time into
Locations 406 (increments of 1 sec) and 407
(increments of 16 sec).
The default value for the Delay Alarm Reporting
Time is 0.
Bosch Security Systems, Inc. | 12/08 | F01U089401-02
ICP-CC404 | Installation Guide | 17.0 System Event Timers
These locations program the time in sec that a
delayed report waits dormant in the dial buffer before
it is sent to the receiving party. If a User Code holder
resets the alarm within this time frame, the control
panel clears the dialer buffer and does not report the
alarm to the receiving party. Refer to Section 14.3.4
Zone Options 1 on page 57 to program zones for delay
alarm reporting.
17.7

Sensor Watch Time

Program Sensor Watch Time into Locations 408
(increments of days, tens digit) and 409 (increments of
days, units digit).
The default value for the Sensor Watch Time is 0.
The time set in these two locations determines the
number of days (0 to 99) a zone can remain sealed
before registering as a fault. This feature is active only
when the system is disarmed. If a zone programmed
for Sensor Watch is not unsealed and reset during this
time, the FAULT indicator lights. Refer to Section 4.13
Fault Descriptions on page 22 for more information on
Sensor Watch Faults. Refer to Section 14.3.4 Zone
Options 1 on page 57 for programming zones for
Sensor Watch.
The Sensor Watch Time counter is active only when
the control panel is disarmed. If the system is
disarmed for 8 hours a day and the Sensor Watch
Time is programmed for 1 day, a zone programmed
for Sensor Watch registers a Sensor Watch Fault if it
is not activated while disarmed within 3 days.
This feature is useful, for example, when someone
places objects in the view of a motion detector,
preventing the detector from picking up movement.
17.8

Codepad Lockout Time

Program the Codepad Lockout Time into
Location 410 (increments of 10 sec).
The default value for the Code Lockout Time is 0.
All codepads are locked out for the programmed time
if an invalid code is entered more times than allowed
by the code retry attempts programmed in
Location 356 (refer to Section 15.19 System Status –
Access Denied on page 63). If the Codepad Lockout
Time is programmed as 0, codepad lockout does not
occur.
17.9

Siren Run Time

Program the Siren Run Time into Location 411
(increments of 1 minute).
The default value for the Siren Run Time is 5.
The Siren Run Time determines how long the horn
speaker operates during an alarm. You can program
the Siren Run Time from 0 to 15 min.

17.10 Siren Sound Rate

Program the Siren Sound Rate into Location 412.
The default value for the Siren Sound Rate is 7.
71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents