Function Assignment Of Input Terminal; Terminal Assignment Of Output Terminal - Mitsubishi Electric FR-A700 Manual

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Pr.
Pr.
178 to 189

Function assignment of input terminal

Pr.178 STF terminal function selection
Pr.180 RL terminal function selection
Pr.182 RH terminal function selection
Pr.184 AU terminal function selection
Pr.186 CS terminal function selection
Pr.188 STOP terminal function selection
Use these parameters to select/change the input terminal functions.
Pr.178 to
Signal
Pr.189
Name
Setting
Pr.59 =0 (initial value)
0
RL
Pr.59 =1, 2*1
Pr.270 =1, 3 *2
Pr.59 =0 (initial value)
1
RM
Pr.59 =1, 2 *1
Pr.59 =0 (initial value)
2
RH
Pr.59 =1, 2 *1
Second function selection
3
RT
Pr.270 =1, 3 *2
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart after instantaneous power
6
CS
failure, flying start
7
OH
External thermal relay input*3
8
REX
15-speed selection (combination with three speeds RL, RM, RH)
9
X9
Third function
10
X10
Inverter operation enable signal (FR-HC/FR-CV connection)
11
X11
FR-HC connection, instantaneous power failure detection
12
X12
PU operation external interlock
13
X13
External DC injection brake operation start
14
X14
PID control valid terminal
15
BRI
Brake opening completion signal
16
X16
PU-external operation switchover
17
X17
Load pattern selection forward rotation reverse rotation boost
18
X18
V/F swichover (V/F cntrol is exercised when X18 is on)
19
X19
Load torque high speed frequency
20
X20
S-pattern acceleration/deceleration C switching terminal
22
X22
Orientation command
23
LX
Pre-excitation (zero speed control/servo lock)
24
MRS
Output stop
25
STOP
Start self-holding selection
26
MC
Control mode swichover
27
TL
Torque limit selection
28
X28
Start time tuning
42
X42
Torque bias selection 1 *4
43
X43
Torque bias selection 2 *4
44
X44
P/PI control switchover
60
STF
Forward rotation command (assigned to STF terminal (Pr.178) only)
61
STR
Reverse rotation command (assigned to STR terminal (Pr.179) only)
62
RES
Inverter reset
63
PTC
PTC thermister input (assigned to AU terminal (Pr.184) only)
64
X64
PID forward/reverse action switchover
65
X65
External/NET operation switchover
66
X66
NET/PU operation switchover
67
X67
Command source switchover
68
NP
Conditional position pulse train sign*4
69
CLR
Conditional position droop pulse clear*4
70
X70
DC feeding operation permission
71
X71
DC feeding cancel
9999
- - -
No function
*1
When Pr.59 Remote function selection= "1 or 2", the functions of the RL,
RM and RH signals change as listed above.
*2
When Pr.270 = "1 or 3", the functions of the RL and RT signals change
as listed above.
*3
The OH signal turns on when the relay contact "opens".
*4
Available only when used with the FR-A7AP.
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.179 STR terminal function selection
Pr.181 RM terminal function selection
Pr.183 RT terminal function selection
Pr.185 JOG terminal function selection
Pr.187 MRS terminal function selection
Pr.189 RES terminal function selection
Function
Low-speed operation command
Remote setting (setting clear)
Stop-on contact selection 0
Middle-speed operation command
Remote setting (deceleration)
High-speed operation command
Remote setting (acceleration)
Stop-on contact selection 1
Pr.
Pr.
190 to 196

Terminal assignment of output terminal

Pr.190 RUN terminal function selection
Pr.192 IPF terminal function selection
Pr.194 FU terminal function selection
Pr.196 ABC2 terminal function selection
You can change the functions of the open collector output terminal
and relay output terminal.
Pr.190 to Pr.196
Setting
Signal
Name
Positive
Negative
logic
logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
2
102
IPF
Instantaneous power failure/undervoltage
3
103
OL
Overload alarm
4
104
FU
Output frequency detection
5
105
FU2
Second output frequency detection
6
106
FU3
Third output frequency detection
7
107
RBP
Regenerative brake prealarm
8
108
THP
Electronic thermal relay function prealarm
10
110
PU
PU operation mode
11
111
RY
Inverter operation ready
12
112
Y12
Output current detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
16
116
RL
PID forward/reverse rotation output
17
MC1
Commercial power-supply switchover MC1
18
MC2
Commercial power-supply switchover MC2
19
MC3
Commercial power-supply switchover MC3
20
120
BOF
Brake opening request
25
125
FAN
Fan fault output
26
126
FIN
Heatsink overheat pre-alarm
27
127
ORA
Orientation in-position *
28
128
ORM
Orientation error *
30
130
Y30
Forward rotation output *
31
131
Y31
Reverse rotation output *
32
132
Y32
Regenerative status output *
33
133
RY2
Operation ready 2
34
134
LS
Low speed output
35
135
TU
Torque detection
36
136
Y36
In-position *
41
141
FB
Speed detection
42
142
FB2
Second speed detection
43
143
FB3
Third speed detection
44
144
RUN2
Inverter running 2
45
145
RUN3
During inverter running and start command is on
During deceleration due to instantaneous
46
146
Y46
power failure (retained until release)
47
147
PID
During PID control activated
64
164
Y64
During retry
70
170
SLEEP
During PID output suspension
84
184
RDY
Preparation ready signal *
85
185
Y85
DC current feeding
90
190
Y90
Life alarm
91
191
Y91
Alarm output 3 (power-off signal)
92
192
Y92
Energy saving average value updated timing
93
193
Y93
Current average monitor signal
94
194
ALM2
Alarm output 2
95
195
Y95
Maintenance timer signal
96
196
REM
Remote output
97
197
ER
Minor fault output 2
98
198
LF
Minor fault output
99
199
ALM
Alarm output
9999
No function
* Available only when used with the FR-A7AP.
Pr.
Pr.
232 to 239
Refer to the section about Pr. 4.
Pr.
Pr.
240
Refer to the section about Pr.72.
Pr.
Pr.
241
Refer to the section about Pr. 125.
Pr.
Pr.
242, 243
Refer to the section about Pr.73.
Pr.191 SU terminal function selection
Pr.193 OL terminal function selection
Pr.195 ABC1 terminal function selection
Function
60