HP 403349-003 Maintenance And Service Manual page 115

Modular cooling system
Table of Contents

Advertisement

NOTE:
This procedure is specifically for the removal of the Type 1 flow meter.
Power down the MCS unit
1.
Shut off the water flowing into the MCS unit
2.
Remove the bottom fan unit
3.
Relocate the power inlet box
4.
Remove the condensation pump and sensors
5.
page 47).
Remove the bottom heat exchanger unit
6.
59).
Remove the magnetic solenoid valve
7.
Remove the AC transfer switch
8.
Using the 46-mm wrench (included in the miscellaneous hardware kit), loosen the two flow meter
9.
union nuts securing the flow meter in place.
To reduce the risk of electric shock or damage to the equipment, use extreme
WARNING:
caution when removing and replacing components that involve water around the electrical
wires and unsecured power inlet box. There is great risk of electrical shock when water is used
near electricity.
WARNING:
To reduce the risk of electric shock or damage to the equipment, be prepared to
clean up the water from the disconnected water line with towels and sponges.
("Powering down the MCS
("Shutting off the
("Removing the bottom fan
("Relocating the power inlet
("Removing the condensation pump and
("Removing the heat exchanger unit with
("Removing the magnetic solenoid
("Removing the AC transfer
Technician repair removal and replacement procedures 115
unit" on page 24).
water" on page 25).
unit" on page 44).
box" on page 93).
valve" on page 82).
switch" on page 26).
sensors" on
couplers" on page