Flow Meter Sensor; Removing The Flow Meter Paddle-Wheel Sensor - HP 403349-003 Maintenance And Service Manual

Modular cooling system
Table of Contents

Advertisement

Using a T-25 Torx driver, secure the horizontal shipping bracket to the MCS unit by inserting four
4.
Torx screws.
Complete the operation checklist (on page 111).
5.

Flow meter sensor

The flow meter sensor is a component of the water group located at the bottom interior of the MCS unit.
The following tools are required for installation:
T-25 Torx driver
Wire cutters
Water hose fitting wrench (included with your original MCS unit)
Counter hold wrench (included with your original MCS Unit)

Removing the flow meter paddle-wheel sensor

Power down the MCS unit.
1.
Shut off the water flowing into the MCS unit.
2.
Remove the bottom fan unit.
3.
("Powering down the MCS
("Shutting off the
("Removing the bottom fan
unit" on page 24)
water" on page 25)
unit" on page 44)
Removal and replacement procedures 54