Using the counter hold wrench to hold the fitting in place and the water hose fitting wrench to tighten
6.
the water hose (both wrenches are included with your original MCS unit), connect the In and Out
water hoses to the heat exchanger unit.
Connect the temperature sensor connector to the heat exchanger unit.
7.
Replace the air deflector plate
8.
Replace the fan unit
9.
Complete the operation checklist (on page 111).
Heat exchanger unit (HEX) with ball valve
The three heat exchanger units are located on the front of the MCS unit.
("Replacing the air deflector
("Replacing the fan
unit" on page 52).
plate" on page 34).
Removal and replacement procedures 67