Part 12 - Troubleshooting; Heater Error Code; Heater Error; Heater Fault - Pioneer PHR100-55 Instruction Manual

Pioneer water heater instruction manual
Table of Contents

Advertisement

2. Design supply water temperature at the minimum design outside temperature: Function 9.
3. Maximum outside design temperature: Function 10.
4. Design supply water temperature at the maximum outside temperature: Function 11.
NOTE: The homeowner can adjust the heat curve down by adjusting the central heating temperature to a
lower setting.
PART 12 – TROUBLESHOOTING
A. HEATER ERROR CODE
An error code may occur in the installation of the heater. This condition may lead to a lock out condition of
the controller, which will need to be manually reset through the
help the installer correct the problem before going into a lock out condition, which will require a manual
reset.
RESISTANCE TABLE FOR
SUPPLY TEMPERATURE
SENSOR
HIGH/LOW
RESISTANCE
TEMP. SENSOR
(ohms)
o
TEMP. (
F)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
202
786
212
667
Table 14
B. HEATER ERROR
1. When an error condition occurs the controller will display an error code
on the display module.
2. These error codes and several suggested corrective actions are
included in Table 15.
C. HEATER FAULT
1. When a fault condition occurs the controller will illuminate the red
"fault" indication light and display a fault code in the format (Example:
|F00|) on the display module.
2. Note the fault code and refer to Table 16 for an explanation of the fault
code along with several suggestions for corrective actions.
3. Press the reset key to clear the fault and resume operation. Be sure to
observe the operation of the unit to prevent a recurrence of the fault.
{S4}
button. These temporary codes will
56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Phr130-55Phr199-55Phr160-55

Table of Contents