Piping - LG DOAS Installation And Operation Manual

Dedicated outdoor air system
Table of Contents

Advertisement

PIPING

Condensate Drain Piping
Condensate Drain Piping
Condensate drain trapping and piping must conform to all applicable codes. A p-trap and drain line must be installed. The p-trap cannot
exceed 6 inches from the drain connection. The lines need to be the same pipe size or larger than the drain connection, include a p-trap, and
pitch downward toward the drain. An air break should be used with long condensate line runs.
Figure 6: Drain Trap
The absolute value of the fan inlet pressure will always be greater than or equal to the absolute value of the static pressure in the drain pan or
draw-through units so the fan inlet pressure is a safe value to use for the drain pan static pressure.
Table 3:DOAS Drain Trap Dimensions
Draw-Through
Drain Pan Pressure
Trap Dimensions
Negative Static
X
(inches of water)
(inch)
-0.50
1.50
-1.00
2.00
-1.50
2.50
-2.00
3.00
-2.50
3.50
-3.00
4.00
-3.50
4.50
-4.00
5.00
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
12
Failure to install p-traps can result in an overflow of condensate water. This can lead to product
damage or property damage. Draw-through cooling coils will have a negative static pressure in
the drain pan area. This can cause an un-trapped drain to back up due to the air being pulled up
through the condensate drain piping.
The value of pressure in the drain pipe should be at least equal to the absolute value of
the negative static pressure in the drain pan plus one inch. Follow the procedure below to
calculate the static pressure.
Calculating Static Pressure
1. Add the pressure drops of all components upstream of the drain plan. This includes the
cooling coil.
2. Add the return duct static pressure. Include the dirt allowance pressure drop for the
filters to account for the worst-case scenario.
Y
(inch)
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
Due to our policy of continuous product innovation, some specifications may change without notification.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arnd20bdat2Arnd20bdar2

Table of Contents