Configuring the LonWorks Network
1. Login to the web user interface.
2. Navigate to the network page. The network page contains four tabs for a LonWorks configured unit. The Lon Device Manager holds a
database of Lon devices with one entry (local Lon device). The local Lon device contains the
definition of the Lon driver properties for the JENEsys controller.
3. Double-click the local Lon device to display a quick view of some of the most important properties for the JENEsys controller and a Lon
device.
Figure 59: Lon Device Properties
4. The Channel ID, Subnet and Node need to be changed to the appropriate value desired by the network supervisor.
5. Click the Save button.
6. Click the Lon Property tab. The Lon Property tab allows you to enable or disable the Lon network. By default, the unit is shipped with the
network disabled.
7. Change the Service Pin.
• Right-click Local Lon Device and click Actions.
• Select Service Pin from the Actions menu.
Figure 60: Service Pin