Interfaces; General; Twisted Pair Interface - ABB SROUT Technical Reference Manual

Router option card for lon star coupler rer 111
Table of Contents

Advertisement

SROUT
4.
4.1.
4.2.
10
Router Option Card for Lon® Star Coupler
RER 111

Interfaces

General

The router option card has five separate interfaces:
- a 64-pin E1 card connector for the connection to the mother board of the
RER 111 unit
- a fibre-optic transceiver pair
- a 9-pin D-type female connector for transformer-isolated twisted pair connection
- a service switch
- a 40-position SIMM connector for the RTR-10 core module.

Twisted pair interface

A 9-pin D-type female connector is used for the transformer-isolated twisted pair
interface. In the picture below the connector is viewed from the outside, looking into
it. The contacts are on top of the connector with pin 1 on the left hand side.
5
4
3
2
9
8
7
6
)LJ  7KH SLQ 'W\SH IHPDOH FRQQHFWRU
Table 4.2.-1 The pin designations for the twisted pair interface
Pin
Signal
1
Net A
2
Net B
For the communication cable specifications regarding the twisted pair network, refer
to the document "Junction Box and Wiring Guidelines For Twisted Pair L
Networks", August 1994. Echelon Corporation.
If a shielded cable is used, the protective shield should be connected to the casing of
the D-type connector. The connector of the option card is earthed to the case of the
RER 111 unit. Figure 4.2.-2 below illustrates the connection of the protective shield
to the cable connector.
The cable connector has to be made of a conductive material.
Protective shield
Conductive casing
)LJ  3URWHFWLYH VKLHOG FRQQHFWLRQ RI WKH WZLVWHG SDLU FDEOH
1
srout_6
Description
Signal line
Signal line
srout_7
1MRS 750109-MUM
W
ON
ORKS
ABB Automation

Advertisement

Table of Contents
loading

Table of Contents