Appendix A - ABB SROUT Technical Reference Manual

Router option card for lon star coupler rer 111
Table of Contents

Advertisement

1MRS 750109-MUM
ABB Automation
Router Option Card for Lon® Star Coupler
RER 111

Appendix A

Default values of communication parameters and routing tables for the router option
card, sides A and B.
These default values are set during manufacturing and they are stored in EEPROM
memory of the Neuron chip. Configuration structure values may be read and written
over the LONWORKS network using Read Memory and Write Memory network
management messages addressed to the router option card (for more details see
LONWORKS Technology Device Data chapter A6: The configuration structure).
Table 1: Configuration structure fields and values programmed for router
option card side A (TP/XF-78 interface) during manufacturing
Field of a structure
channel_id
location
comm_clock
input_clock
comm_type
comm_pin_dir
preamble_length
packet_cycle
beta2_control
xmit_interpacket
recv_interpacket
node_priority
channel_priorities
collision_detect
bit_sync_threshold
filter
hysteresis
cd_to_end_packet
cd_tail
cd_preamble
non_group_timer
nm_auth
preemption timeout
.
Table 2: Default routing parameter values for router option card side A (TP/
XF-78 interface).
Routing algorithm:
Router mode:
Value
Offset
/ # of bits
0x0000
0x0016
0
0x02
4
0x08
5
5
0x09
0x0C
6
0x0A
4
0x0B
0
0x0C
0
0x0D
0
0x0E
0
0x0F
30
0x10
0
0x11
0
1
2
0
0x12
0
0
0
0x18
0
5
Repeater
Normal
SROUT
Remarks
/ 16
/ 6*8
set during installation
/ 5
= input_clock / 8: 78kbit/s
/ 3
= 10 Mhz
/ 3
= differential
/ 5
= dir.mode - differential
= 240 µs
/ 8
/ 8
= 4 ms
/ 8
/ 8
/ 8
/ 8
= no priority slot allocated
/ 8
number of priority slots
/ 1
= disabled
/ 2
= number of bits: 4
/ 2
/ 3
/ 6
/ 1
/ 1
/ 4
= 128 ms
/ 1
= no authentication
/ 3
= 10 sec