Main circuit terminal specifications
FR-A740-01440, 01800-NA
R1/L11 S1/L21
Screw size (M4)
R/L1 S/L2 T/L3
Power
supply
FR-A740-03250, 03610-NA
R1/L11 S1/L21
R/L1 S/L2 T/L3 N/-
P/+
Power supply
Screw size (M12)
(for option)
CAUTION
· The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable
to the U, V, W of the inverter. Doing so will damage the inverter. (Phase sequence needs not to be
matched.)
· Connect the motor to U, V, W. At this time, turning on the forward rotation switch (signal) rotates
the motor in the counterclockwise direction when viewed from the motor shaft.
· When wiring the inverter main circuit conductor of the FR-A740-04320 or more, tighten a nut from
the right side of the conductor. When wiring two wires, place wires on both sides of the conductor.
(Refer to the drawing on the right.) For wiring, use bolts (nuts) provided with the inverter.
20
Charge lamp
Jumper
Screw size(M10)
N/-
P/+
P/+
IM
Motor
DC reactor
Screw size
(M10)
Screw size (M4)
Charge lamp
Jumper
Screw size (M12)
P/+
Screw size
(M10)
P/+
IM
Motor
DC reactor
FR-A740-02160, 02600-NA
R1/L11 S1/L21
R/L1 S/L2 T/L3 N/-
P/+
Power supply
Screw size (M12)
(for option)
FR-A740-04320 to 09620-NA
R1/L11 S1/L21
R/L1 S/L2 T/L3 N/-
Power supply
Screw size (M4)
Charge lamp
Jumper
Screw size (M10)
P/+
Screw size
(M10)
P/+
IM
Motor
DC reactor
Screw size (M4)
Charge lamp
Jumper
Screw size (M12)
P/+
P/+
IM
Motor
DC reactor
Screw size (M10)