5.3 Auxiliary function setting mode 1
Character
(PV display)
Set value lock selection
• Locks the set value to prevent setting errors.
The setting item to be locked depends on the selection.
If Lock 1 or Lock 2 is selected, PID auto-tuning or auto-reset cannot be carried out.
Sensor correction setting
• Sets the sensor correction value for the sensor.
• Thermocouple, RTD input: –100.0 to 100.0
DC voltage, current input: –1000 to 1000 (The placement of the decimal
point follows the selection)
Communication protocol selection
• Selects the communication protocol.
• Available only when Serial communication (option) is applied.
• Not available if
• Modbus ASCII mode:
Instrument number setting
• Sets the instrument number. (Communication cannot be carried out unless an
instrument number is individually set when communicating by connecting plural
instruments in serial communication.)
• Available only when Serial communication (option) is added.
• 0 to 95
Communication speed selection
• Selects a speed to be equal to the speed of the host computer.
• Available only when Serial communication (option) is added.
• 2400bps:
Parity selection
• Selects the parity.
• Not available if Serial communication (option) is not added or if
is selected during the Communication protocol selection.
• No parity:
Stop bit selection
• Selects the stop bit.
• Not available if Serial communication (option) is not added or if
is selected during the Communication protocol selection.
• 1 or 2
5.4 Auxiliary function setting mode 2
Character
(PV display)
Input type selection
• The input type can be selected from thermocouple (10 types), RTD
(2 types), DC current(2 types) and DC voltage(4 types), and the unit
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
Name, Description, Setting range
(Unlock): All set values can be changed.
(Lock 1): None of set values can be changed.
(Lock 2): Only main setting mode can be changed.
(Lock 3): All set values except input type and Controller/Converter function
can be changed. However, they return to their previous value after power is
turned off because they are not saved in the non-volatile memory. Be sure to
select Lock 3 when changing the set values frequently via communication
function, (If the value set by the communication function is the same as the
value before the setting, the value will not be written in the non-volatile memory.)
Do not change any setting item in Auxiliary function setting mode 2. If any item in
the mode is changed, it will affect other setting items such as SV and Alarm value.
is indicated
, 4800bps:
, Even parity:
Name, Description, Setting range
–200 to 1370 :
–199.9 to 400.0 :
–200 to 1000
:
0 to 1760
:
0 to 1760
:
0 to 1820
:
–200 to 800
:
–199.9 to 400.0 :
–200 to 1300
:
0 to 1390
:
0 to 2315
:
–199.9 to 850.0 :
( )
, Modbus RTU mode:
, 9600bps:
, 19200bps:
, Odd parity:
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26) 0 to 4200
Pt100
7
Default value
(SV display)
Unlock
0.0
0
9600bps
Even parity
1
Default value
(SV display)
K
(–200 to 1370 )
/
can be selected.
–320 to 2500
:
–199.9 to 750.0 :
–320 to 1800
:
0 to 3200
:
0 to 3200
:
0 to 3300
:
–320 to 1500
:
–199.9 to 750.0 :
–320 to 2300
:
0 to 2500
:
:
–199.9 to 999.9 :