Alarm action delayed timer setting
• Sets the alarm action delayed time.
When the setting time has passed after the input enters alarm output range, the
alarm is activated.
• Not available if No alarm action is selected during the Alarm type selection.
• 0 to 9999 seconds
Direct/Reverse control action selection
• Selects either Reverse (Heating) or Direct (Cooling) control action.
• Reverse (Heating) action :
Direct (Cooling) action
AT bias setting
• Sets bias value during PID auto-tuning.
• Not available for the DC voltage or current input
• 0 to 50
Setting item not used: This item is indicated when Serial communication (option) is
Output status selection when input abnormal
• Selects the output status of OUT when DC input is overscale or underscale.
See "Input abnormality indication" on page 18.
• Available only for DC current output with DC input
Controller/Converter function selection
• Selects either controller or converter function.
• Available only when the control output is DC current output type.
• Controller function:
Converter function:
ARW function
ARW (Anti-reset windup) prevents overshoot caused by the integral action. The smaller the ARW value, the less
the overshoot caused by the integral action in the transition status, however it takes time until stabilization.
Sensor correction function
This corrects the input value from the sensor. When a sensor cannot be set at a location where control
is desired, the sensor measuring temperature may deviate from the temperature in the controlled
location. When controlling with plural controllers, the accuracy of sensors affects the control. Therefore,
sometimes the measured temperatures (input value) do not concur.
In such a case, the control can be set at the desired temperature by adjusting the input value of sensors.
Energized/Deenergized function
When [alarm action Energized] is selected, the alarm output (between terminals 8-9) is conducted (ON)
while the alarm output indicator is lit.
The alarm output is not conducted (OFF) while the alarm output indicator is not lit.
When [alarm action Deenergized] is selected, the alarm output (between terminals 8-9) is not conducted
(OFF) while the alarm output indicator is lit.
The alarm output is conducted (ON) while the alarm output indicator is not lit.
[This function is not available for the Loop break alarm and Heater burnout alarm (optional).]
ON
OFF
SV setting
High limit alarm (When Energized is set)
5.5 Output MV (manipulated variable) indication
Output MV (manipulated variable) indication
• In the PV/SV display mode, press the
Keep pressing the
setting mode appears temporarily during the process.
(The SV display indicates output manipulated variable and the 1st decimal point from the right
flashes in 0.5 second cycles)
If the
key is pressed again, the unit reverts to the PV/SV display mode.
(0 to 100 ) or 0.0 to 50.0
added. However, this cannot be used.
: OFF(4mA) or OUT low limit
: Outputs a value between OFF (4mA) and ON (20mA) or between OUT low
limit value and OUT high limit value, depending on a deviation.
A1 hysteresis
+ A1 set point
(Fig. 5.4-1)
Name and Description
key until the output manipulated variable appears, though the main
:
(0.0 to 100.0 )
A1 hysteresis
ON
OFF
+ A1 set point
SV setting
High limit alarm (When Deenergized is set)
(Fig. 5.4-2)
key for approx. 3 seconds.
9
0 seconds
Reverse (Heating) action
20
Output OFF
Controller function