6 Using the System

6.9 System Con guration Changes

An alarm message like the following appears when a system con guration change (or the
possibility of a con guration change) is detected.
If the system continues to operate after its con guration has changed, distribution ratios and other
data will be totally inaccurate. For this reason, cut-off processing must be done with the system
in the state before the change. The following message is displayed to ask you to con rm the
processing.
Operation procedure for each case is as follows.

6.9.1 When a system con guration change detected

This alarm message is displayed in cases such as the following.
1 "Check system Con guration" was made after removing
the outdoor and indoor units.
2 "Check system Con guration" was made after starting the
unit and found that it was different from the previous one
in con guration.
* "Con guration" includes not only the number of units and
address but also indoor unit capacity, main/sub unit setting,
and presence/absence of an electric heater.
Here you can see the link system where the con guration has
been changed.
While this message is visible, no other operations can be performed except OK and Cancel .
Touch OK to perform cut-off processing with the system in the state before the change.
Touch Cancel if you do not need to perform cut-off processing.
Touch OK to check the new con guration.
If you select OK here, the current system con guration is
re-checked and the results are con rmed.
If you do not need to do this, select Cancel .
If the system has changed because of a mistake, return the system to its former state and then
touch Cancel . You should also touch Cancel here if you mistakenly selected Cancel in the
previous message, even though the system cut-off processing should have been done. This
returns you to the rst alarm message, where you can perform cut-off processing.
While this message is visible, no other operations can be performed except OK and Cancel .
74
6 Using the System

6.9.2 When system con guration may change

This alarm message is displayed in cases such as the
following.
1 The following "Detailed settings" were made from a local
remote controller.
(for address, extension settings, indoor unit capacity, or
presence/abesnce of an electric heater)
2 Only con rmation of "Detailed setting" was made from a
local remote controller.
3 Automatic address setting was carried out for an indoor
or outdoor unit.
4 An additional indoor or outdoor unit was installed.
* "Con guration" includes not only the number of units and
address but also indoor unit capacity, main/sub unit setting,
and presence/absence of an electric heater.
While this message is visible, no other operations can be performed except Do later. or
Do now. .
When touching Do later. , this window closes and other screen operations are made possible.
However, after a while the message will be displayed again.
Touch Do now. to con rm whether the con guration has been actually changed.
When a con guration change was detected as a result of con guration con rmation, cut-off
processing is automatically performed and the post-variation con guration is established. When
there is no change in con guration, the screen exits con guration con rmation processing.
For example, imprudently pressing Do now. while a communication error message is displayed
will result in an automatic cut-off processing to establish the current con guration. Therefore,
take full care to avoid such a mistake.
When establishing a con guration without making cut-off processing, press Do later. to once
close the screen and perform "Check system Con guration" using the 6-9 screen.
After this, proceed "Perform cut-off?"
"Cancel"
"OK" in accordance with "6.9.1. When a system con guration change detected".
When no operation has been made on this screen for twelve hours or more, cut-off and post-
variation con guration xing processing are automatically carried out.
Imprudent cut-off processing and con guration xing or neglecting them when necessary may
cause a signi cant inconvenience in control.
When this alarm message is displayed, do not operate the system and contact the store where
you purchased it or its service agency.
This message may be displayed also in inspecting the air conditioner. In such a case inform the
person in charge of service of the fact.
75
"Con rm the current system con guration?"
Caution