Features Of The System; System Con Guration - Panasonic CZ-256ESMC2 Operation Manual

Centralized control system intelligent controller
Hide thumbs Also See for CZ-256ESMC2:
Table of Contents

Advertisement

2 Features of the System

The Intelligent Controller is a centralized air conditioning management system dedicated to PAC and GHP for small
and medium sized buildings.
Number of connectable units ········ • By connecting communication adaptors to one Intelligent Controller, up to
256 indoor units can be connected.
• Up to 120 outdoor units can be connected.
Display ·········································· • Touch panel type 6.5-inch TFT color (640x480 pixel VGA) LCD display
Operation functions ······················· • Start and stop, temperature settings, operation mode selection, fan speed
settings, fan direction settings, ventilation etc.
Operating monitoring ···················· • All unit monitoring of operation status (operating/stopped, operation
mode, alarms)
• Display of alarm logs
• One-operation checking of all filter cleaning signs and engine oil
inspection signs
• External output of all errors, external output of all operations (relay
connections)
Program timers ........................ • Up to 50 types of weekly timers can be programmed by combining 50
types of daily timers (50 times per day).
Air conditioning energy
distribution ····································· • Recording and display of accumulated operating time and total number
of operations for each indoor unit.
• Calculation of gas and electricity distribution ratios and energy amounts
used (m
3
, kWh) for each indoor unit and each tenant.
• Distributions are available in two modes: the "simple distribution" calculated
based on the operating time and "loaded distribution" calculated based
on the actual air conditioning capacity, respectively. (In order to make
operation in the "Loaded distribution" mode, the air conditioner side needs
to be adaptable to the "Loaded distribution".
• Distribution by time zones (regular hours, out of hours, special days).
• Recording of up to past 24 months of cut-off data.
Printing display ····························· • All operating screens can be printed out with a dedicated printer connected
(hardcopy).
Terms and abbreviations used in this manual and in the system software
Full term
Adaptor address
Adaptor
Link system address
Link system
Outdoor unit system address
Outdoor unit system, Outdoor unit, Outdoor system, Outdoor, O/D
Indoor unit address
Indoor unit, Indoor, I/D
Distribution group number
Distribution group No., Distribution group
Tenant number
Tenant No., Tenant
Zone number
Zone No., Zone
Unit name
Unit
Air conditioning distribution ratio
Distribution ratio, Distr. ratio
Central control address
Central address, CNTR
Thermostat
T/S
* For more information about terms, see "11 Terms".
8
Abbreviation

3 System Con guration

System Con guration Example
Intelligent Controller
Inter-unit control wire
Link system
(non-polar)
Link system
Pulse meter x 3
No.2
All-unit signal x 4
Inter-unit
control wire
(non-polar)
Communication adaptor
control wire
Communication adaptor
(RS-485, polar)
Pulse meter x 3
All-unit signal x 4
Link system
No.4
Communication adaptor
Pulse meter
G
All-unit signal x 4
W
G: Gas flow meter
Independent installation
W: Electricity meter
without link system
connection also possible
* When connecting link systems (Inter-unit control wires), always connect beginning with LINK1 and LINK2 on the
Intelligent Controller. Up to 4 link systems can be connected.
9
No.1
Link system
No.3
Maximum number of connections
Indoor units:
256 (64/link x 4)
Outdoor units:
120 (30/link x 4)
Communication adaptors:
7
Link systems:
4
(Inter-unit control wires)