Ceiling type
CAUTION
Fix the power supply wires and the control wires/remote control wires separately with the cord clamp as show below.
Connected at backside
Cord clamp
Conduit pipe
Cord clamp
Hole for remote control
wires and control
wiring
Connected at upside
Cord clamp
Attach the supplied
bushing to seal the
back side conduit hole.
19-EN
Installation Manual
Conduit hole for
power supply wires
Conduit hole (knockout)
for power supply wires
Hole for remote control
wires and control
wiring
(knockout)
Attach the supplied
bushing to cover the
hole edge.
Cord Clamp
Cord Clamp
Ceiling type
Power supply wires and
ground wire
1. Strip the wire ends.
Power supply wire: 0.4" (10 mm)
Ground wire: 0.8" (20 mm)
2. Match the wire colors with the terminal numbers on
the indoor units' and circuit breakers' terminal blocks
and firmly screw the wires to the corresponding
terminals.
3. Secure the ground wire with the ground screw.
4. Fix the wires with a cord clamp.
Unit: in (mm)
0.8" (20)
1.2" (30)
L
L
1
2
0.4" (10)
Ground wire
CAUTION
Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it
is connected to the terminal block.
Power supply wires and control
wire
– 10 –
Installation Manual
Control wires
Because a "hole for control wires and remote control
wires" has little space, a cover of control wires (2-core
shielded wire) should be removed up to 10" (260mm).
Hole for control wire and
Remote control wires
Electrical control
Ground screw for
box
shielded wire
Power supply wires
2" (50)
Cover
Shield wire
0.4" (9)
10" (260)

Address setup

Set up the addresses as per the Installation Manual
supplied with the outdoor unit.
EN
20-EN