LG BECON HVAC BACnet PQNFB17C1 Installation & User Manual page 19

Hide thumbs Also See for BECON HVAC BACnet PQNFB17C1:
Table of Contents

Advertisement

The maximum quantity of connected indoor unit is different depending on the quantity of
connected I/O modules.
Please refer to following information related to product connection quantity.
Quantity of
Device
256
128
* Devices: Indoor units, ERV, DI/DOs, DOKITs, AWHPs, AHUs
• RS-485 communication cable connection
- There is a polarity in RS-485 communication cable connection, so be careful not to reverse
the connection of the two cables.
- Do not let the length of RS-485 communication cable exceed total of 1 km.
- RS-485 communication cable must be connected with BUS type.
• IP address of the ACP BACnet
- IP address of the ACP BACnet, address of Gateway, and Net mask must be requested to the
person in charge of the network of the corresponding site.
Caution
RS-485 Connection of the ERV equipment
To connect ERV equipment, it is recommended to use the ports other than RS-485
communication ports which are connected to air conditioners.
16
Quantity of I/O Module
INSTALLING ACP BACnet