1.
Hold the handles on the chassis or support the chassis bottom and steadily move the chassis to the
workbench or floor.
2.
Gently put the chassis on the workbench or floor.
3.
Attach the L-shaped brackets to the workbench or floor with wall anchors.
Figure 14 Attaching L-shaped brackets with wall anchors
(1) Fastening screw
(3) Wall anchor
Grounding the switch
CAUTION:
Before using the switch, connect the grounding cable correctly to guarantee lightning protection and
anti-interference of the switch.
Grounding the switch with a grounding strip
CAUTION:
•
Use the supplied grounding cable (yellow-green grounding cable).
Connect the grounding cable to the earthing system in the equipment room. Do not connect it to a fire
•
main or lightning rod.
If a grounding strip is available at the installation site, connect the grounding cable through the
grounding strip.
To connect the grounding cable:
1.
Unpack the grounding cable.
The grounding cable provided with the switch is compliant with the NEBS standards.
(2) L-shaped bracket
18