Physical Ports
Figure 2-4 Bottom and top views of the NetCol5000-C
1. Bottom outlet for the power and PE
cables
3. Bottom water outlet pipe
5. Bottom water inlet pipe
7. Top water outlet pipe
9. Top outlet for power line and PE
line
Table 2-1
Table 2-1 The diameter of pipes and cables
Content
Water inlet and outlet pipe
Forcible drainpipes
Condensate Drainpipes
Machine power supply core
PE line (Outside the cabinet)
Issue 02 (2013-12-10)
lists the diameter of pipes and cables requirements.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2. Bottom outlet for the signal cable and forcible
drainpipe
4. Condensate drainpipe port
6. Reserved hole for humidifier pipe
8. Top water inlet pipe
10. Top outlet for the signal cable and forcible
drainpipe
Specification
DN25 (Recommended diameter, prepare it by yourself)
Standard configuration: Φ=4 mm (OD Φ=7 mm), length =
5 m
Standard configuration: Φ=10 mm (OD Φ=14 mm),
length = 2 m
2
2 × 2.5 mm
(Recommended diameter, prepare it by
yourself)
2
≥ 6 mm
(Recommended diameter, prepare it by yourself)