Figure 5-41 Teamwork setting page 2
Table 5-3 Teamwork settings
Parameter
Teamwork unit
no.
Teamwork unit
address
Teamwork
function
Network
Total number
of units
Number of
running units
Standby mode
Issue 02 (2013-12-10)
Description
A maximum of four groups (1 to 4)
can be set.
Set an address (1 to 32) for each
temperature control device in each
group. Devices in the same group
cannot have the same address and
the address of the master device in
each group should be 1.
Disable or enable the teamwork
function. If disabled, this device is
operating according to its own
control. If enabled, this device
works in harmony with others that
in the same group.
Networking mode for the
teamwork.
Number of the temperature control
devices in this group (1 to 32 can be
set).
Number of the active devices (1 to
[total number of units] can be set).
If the number is more than the
range, the excessive one(s) cannot
be group-controlled. If one address
is vacant, the topology will display
that the device is off-line.
Disable or enable the active and
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Controller Operate Guide
Configuration Principle
Group the temperature control
devices in adjacent areas as one,
that is, assign one group number
for them.
Only one device in each group
can be set to 1.
Set this parameter based on the
onsite device heat distribution.
Networked over CAN.
Total number of the temperature
control devices in this group
Assign the devices to be active
ones by the device number,
beginning with the master one.
The rest will become the standby
ones.
This function is recommended
83