NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual Issue Date 2017-07-27 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document Purpose This document describes the NetCol5000-A air cooled in-row precision air conditioner in terms of its product overview, installation, power-on commissioning, operation and maintenance (O&M), and FAQ. It helps readers understand how to use and maintain the NetCol5000-A.
Page 4
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual About This Document Symbol Description Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual Contents Contents About This Document ........................ii 1 Safety Precautions ......................... 1 1.1 General Safety ................................1 1.2 Electrical Safety ................................2 1.3 Mechanical Safety ................................ 4 1.4 Operating Safety ................................5 1.5 Others....................................
Page 6
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual Contents 3.6 Install Process ................................40 3.7 Installing Indoor Units ..............................41 3.7.1 Installing the Air Conditioner Cabinet (with Base) ....................41 3.7.2 Installing the Air Conditioner Cabinet (Without Base) .................... 46 3.7.3 (Optional) Installing the Enclosure Frame .......................
Page 7
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual Contents 4.7 Charging the Remaining Refrigerant ........................118 4.8 Startup wizard ................................118 4.9 (Optional) Power-off ..............................126 4.10 Checking After Commissioning ..........................127 5 Operation and Maintenance ....................128 5.1 Routine Maintenance ..............................
Page 8
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual Contents 6.8 Deleting Historical Alarms ............................226 6.9 Deleting Logs................................226 6.10 Exporting Data ................................ 227 6.11 Clearing the Runtime .............................. 228 6.12 Calibrating a Sensor ..............................229 6.13 Calibrating the Screen ............................. 230 6.14 How to Perform Quick Settings ..........................
1 Safety Precautions Safety Precautions 1.1 General Safety Declaration Huawei shall not take responsibility for any damage caused by any of the following: Operation under severe environments which are not specified in this document. Usage under installation and operating environments which are not specified in related international specifications.
Only trained and qualified personnel are allowed to install, operate, and maintain the equipment. Only personnel certified or authorized by Huawei are allowed to replace or modify the equipment or components (including software). Any fault or error that might cause safety problems must be reported immediately to a supervisor.
Page 11
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 1 Safety Precautions The device is powered by a high-voltage power supply. Direct or indirect contact (through damp or conductive objects) with high-voltage power sources will result in serious injury or death.
Metal shavings from drilling may block pipes and cause short circuits in circuit boards if they enter the cabinet. Only drill with the approval of the customer, contractor, and Huawei. Remove interior cables before drilling holes into a cabinet.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 1 Safety Precautions Move the equipment close to the installation site before unpacking. Unpack the equipment with caution to avoid scratching or bumping it. Unload the equipment from the pallet immediately before installation.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 1 Safety Precautions Low-temperature component: evaporator. High Rotational Speed High-speed rotating component: fan. 1.5 Others Binding Signal Cables Signal cables must be bound separately from power cables with a spacing of at least 50 mm.
(7) Signal cable hole (Φ28 mm) on the skylight 2.2.2 Cooling Components The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan, evaporator, electronic expansion valve (EEV), oil separator, sight glass, filter dryer, air filter, electric heater (optional), wet film humidifier (optional), condensate pump, check valve, differential pressure switch, and temperature and humidity sensor (T/H sensor).
Page 19
(20) Filter dryer Compressor − The NetCol5000-A uses a DC variable-frequency compressor that features compact size, light weight, long service life, low noise, easy installation as well as high reliability, stability, and energy efficiency. − The high-precision drive automatically adapts to the system pressure fluctuations.
Page 20
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description − There are ten EC fans in total. The air conditioner will not shut down when a single fan fails. − Fans can be maintained with power-on. You can replace one faulty fan without shutting down the air conditioner.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description − The wet film humidifier consumes less power, saving more than 95% of energy compared with a traditional electrode humidifier. − Compared with a traditional electrode humidifier, the wet film humidifier has a longer service life and maintenance interval.
Page 22
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description Table 2-2 Indicator and buzzer status description Alarm Status Indicators Buzzer The device is operating properly, or a warning Green Silent alarm occurs. The buzzer keeps buzzing if a major alarm is...
Page 23
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description The 7-inch display panel with the true-color touchscreen allows you to set parameters for the air conditioner and query its status. The air conditioner has the following three remote functions.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description Password verification is required upon the first startup to ensure the system security. No password verification is required for subsequent startup if the first verification succeeds.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description Item Specifications Outdoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch (15.88 mm), welding Refrigerant gas pipe Outer diameter of 7/8 inch (22.22 mm), welding...
Page 26
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description Table 2-6 Optional specifications Item NetCol5000-A0 NetCol5000-A0 NetCol5000-A0 NetCol5000-A0 42H413D20020 42H413D20020 42H413D2W12 42H413D2W12 Power 380–415 V AC, 50 Hz or 60 Hz 3Ph+N+PE system Tolerance: –10% to +10% of rated voltage, rated frequency± 3 Hz...
Page 27
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 2 Product Description Operating Specifications temperature Protection level IP20 Installation Floor or ESD floor-mounted mode Pipe and cable Pipes and cables routed from the top or bottom routing 0–4000 m. When the altitude exceeds 1000 m, the power should be Altitude derated.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Installation Guide 3.1 Installation Precautions Installation Requirements If the actual server total load for each air conditioner is less than 10% of rated cooling capacity or the equipment room is not properly sealed, the humidity in the equipment room may be too high, which is not a product quality issue and should be dealt with by adding a dehumidifier.
Page 29
(RCCB) that is not sensitive to the single-phase DC pulses and transient current pulses. Note: If the requirements are not met, contact Huawei technical support for an optimized solution. Space Requirements ...
To ensure the optimal operating condition and longest service life, install the NetCol5000-A in strict accordance with requirements. 3.2.1 Tools The following tables list the tools for installing the NetCol5000-A. Add or delete tools as required. Issue 01 (2017-07-27) Huawei Proprietary and Confidential...
Page 31
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Table 3-2 General tools Appearance, specifications, and name Phillips screwdriver Flat-head Socket wrench (18 Adjustable wrench (M4, M6, and M8) screwdriver (M3 and Torque wrench (28...
Page 32
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Table 3-3 Transporting tools Appearance, specifications, and name Electrical pallet Lifting rope (bearing Lever (bearing at Manual pallet truck truck at least 400 kg) least 400 kg)
Page 33
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Table 3-5 Connecting cable tools Appearance, specifications, and name Polyvinyl chloride ESD gloves Insulation gloves Wire stripper (PVC) insulation tape Heat gun Crimping plier Table 3-6 Commissioning tools...
Engineering purchase: This material will not be delivered by Huawei, and customers need to purchase it. 3.2.2.1 (Optional) Refrigerant R410A Do not use low-quality refrigerant. Huawei is not responsible for any damage caused by low-quality refrigerant. Follow these suggestions to choose high-quality refrigerant: Use high-quality brands such as DuPont, Daikin, or Honeywell.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Temperature Saturation Temperature Saturation Temperat Saturation (° C) Pressure-S (° C) Pressure-S ure (° C) Pressure-S urface urface urface Pressure Pressure Pressure (MPa) (MPa) (MPa) 1.31 2.21...
Page 36
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Oil trap and inverted trap: Install an oil trap every five to six meters in the vertical direction along the gas pipe and an inverted trap for the inlet and outlet of the outdoor unit to ensure system reliability.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.2.2.3 (Optional) Humidifier Water Inlet Pipe Humidifier water inlet pipes are not required by the models without heating or humidification functions. The humidifier water inlet pipe can be connected using a hose or a rigid pipe.
Page 38
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-5 Connecting a drainpipe (1) Connector with inner screw threads: (2) Conversion adapter: BSPT 1/2 inch; BSPP 1/2 inch; delivered with air connected to a rigid pipe with external...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.2.2.5 Pipe Support Figure 3-7 shows supports for refrigerant pipes and water pipes. The actual appearance of the supports will be different based on onsite situations.
Page 40
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Installati Item Specifications Remarks Scenario supply: 1 PCS Naked crimping terminal, OT, 10 Delivered with the terminal , M6, 60 A, tin plating, naked fittings ring terminal...
22UL1007, black), (2 x T0.5 orange) 3.2.3 Installation Layout Principles Layout principles for installing the NetCol5000-A are as follows: If the outdoor unit is placed higher than the indoor unit, the vertical distance between them should be less than or equal to 30 m. An oil trap should be installed every 5 m to 6 m in the vertical direction along the gas pipe to ensure system reliability.
Page 42
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide When calculating the height difference, the compressor base is regarded as the baseline for the indoor unit, and the condenser top is regarded as the baseline for the outdoor unit.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-9 Top pipe routing scenario (1) Inverted trap (2) Oil trap (3) Tilted gas pipe (4) Tilted liquid pipe 3.3 Unpacking Procedure Step 1 Inspect the outer packing for signs of damage. If any damage is found, contact the shipping company immediately.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-10 Unpacking Inspect the cabinet exterior for signs of collision or scratches. If any damage is found, contact the shipping company immediately. Step 3 Check the type and quantity of fittings against the packing list. If fittings are missing or inconsistent with those in the packing list, record the information and contact your local Huawei office immediately.
Page 45
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-11 Removing an air filter If the baffle plates cannot be rotated manually, loosen the screws that secure the baffle plates using a Phillips screwdriver until they can be rotated open manually.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-13 Removing the screws Step 2 Remove the cabinet from the pallet. ----End 3.5.2 Removing the Transport Fasteners from the Compressor Procedure Step 1 Loosen the three bolts on the compressor transport fasteners using a 13# solid wrench.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-14 Removing the transport fasteners from the compressor Do not remove the bolts directly. Put away the removed transport fasteners so that you can reinstall them if the indoor unit is to be transported again in the container scenario.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-15 Process for installing an indoor unit 3.7 Installing Indoor Units 3.7.1 Installing the Air Conditioner Cabinet (with Base) Procedure Step 1 (Optional) Make the base.
Page 50
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-16 Base (Unit: mm) Shock absorption bars (EPDM rubber, 5 mm thick) are need to install between the ground and the base. 1100 mm depth: D1 = 1100 mm, D2 = 980 mm. 1200 mm depth: D1 = 1200 mm, D2 = 1080 mm.
Page 51
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Making cable holes on the floor is required only when the cables or pipes are routed from the bottom and there is an ESD floor under the air conditioner.
Page 52
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Do not remove the anchor bolts. Otherwise, rework is required if the cabinet height does not meet requirements. Anchor bolt adjustment method: Rotate anchor bolts clockwise to raise the cabinet and rotate them counterclockwise to lower the cabinet.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-20 Securing a cabinet ----End 3.7.2 Installing the Air Conditioner Cabinet (Without Base) Procedure Step 1 Determine the position for installing the cabinet. Mark mounting holes based on the drawings,...
Page 55
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-21 Distances between mounting holes (unit: mm) Step 2 Drill a hole in each mounting hole position using a hammer drill. Step 3 Move the cabinet over its castors to the installation position.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-22 Securing a cabinet ----End 3.7.3 (Optional) Installing the Enclosure Frame Procedure Step 1 Open the front door. Remove the power cable of the display screen, FE cable, and the ground cable for the front door.
Page 57
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-23 Installing an enclosure frame The positions of the bolt fixing plate, hinges, and connecting plates vary depending on the cabinet model. Step 5 Secure one top sealing plate to the enclosure frame using four M5 tapping screws.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-24 Installing a top sealing plate Step 6 Install the hinges and connecting plates removed in Step 2 on the corresponding positions on the enclosure frame.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Procedure Step 1 Remove the bonnet of the low-pressure needle valve shown in Figure 3-25 and connect the pressure gauge leather hose to the needle valve.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide The thickness of heat insulation cottons should not be less than 9.2 mm. When purchasing water pipes, ensure that the water pipe with thermal insulation foam warped can go through the ports on the bottom and top boards.
Page 61
7/8 inch (22.22 mm) 3/4 inch (19.05 mm) If the one-way pipe length is longer than 100 m, contact Huawei technical support. To dampen noises generated by the equipment due to vibration, refrigerant pipe supports should be installed as required by Figure 3-26.
Page 62
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-26 Routing the refrigerant pipe Onsite personnel are responsible for preparing the required materials and installing the supports. Bottom Pipe Routing Step 1 Remove the plugs from the bottom refrigerant pipe using a welding torque, as shown in Figure 3-27.
Page 63
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Be careful during welding to avoid burning components, such as rubber rings, inside the cabinet. Use a rubber hose to connect the nitrogen cylinder which connecting the reducing valve and the end of the copper pipe, then fill nitrogen at 0.03–0.05 MPa into the copper pipe to...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-29 Top pipe routing (1) Gas pipe (2) Liquid pipe Step 2 Connect the gas and liquid pipes to the gas and liquid pipes of the outdoor unit respectively.
Page 65
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide threads: G 1/2 inch, delivered with adapter: G 1/2 inch; connected made of PP-R or the water inlet pipe for the air to a rigid pipe with outer screw...
Page 66
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Top Pipe Routing When routing pipes from the top, do not route the pipes over servers. If unavoidable, take measures to protect the servers from being affected by pipe leaks.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.9.3 Connecting the Drainpipe Context The drainpipe can be connected using a hose or a rigid pipe. Figure 3-5 shows how to connect the pipe.The following uses rigid drainpipe routing as an example to describe how to connect drainpipes.
Page 68
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-34 Bottom pipe routing Step 2 Install the water pipe conversion adapter and seal it with sealant, as shown by (2) in Figure 3-34. Step 3 Cut a cross in the rubber ring using a utility knife and route the pipe wrapped with the thermal insulation tube through the hole.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-35 Top pipe routing Step 2 Route the drainpipe from the top by referring to Step 2–Step 5 of the bottom pipe routing. ----End 3.10 Leak Checking Prerequisites ...
Page 70
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-36 Charging nitrogen to pipes without configuring low-temperature component (1) Nitrogen cylinder (2) Reducing valve (3) Low pressure gauge (4) High pressure gauge (5) Low-pressure needle valve (6) Exhaust pipe needle valve ...
Page 71
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-37 Charging nitrogen to pipes with installing low-temperature component (1) Nitrogen cylinder (2) Reducing valve (3) Pressure gauge 1 (4) Pressure gauge 2 (5) Connection nut...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.11 Connecting Cables 3.11.1 Connecting the Power Cable Before connecting cables, remove the top cover of the indoor unit power terminals. Power cables can be routed from the top or bottom.
Page 73
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-38 Routing cables for the single power supply Step 2 Connect the PE cable to the cabinet ground bar, as shown in Figure 3-38. ----End...
Page 74
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-39 Routing cables for the dual power supplies Step 2 Connect the PE cable to the cabinet ground bar, as shown in Figure 3-39. ----End...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.11.2.1 Connecting the Outdoor Unit On/Off Signal Cable Context The outdoor unit signal cable can connect to a dry contact or an RS485 port (by default).
Page 77
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-41 Connecting the outdoor unit on/off signal cable (RS485 connection) (Dry contact connection) Connect one end of the cable to points 1 and 2 on the external signal port X301 and the other end to ports 1 and 2 on the outdoor unit.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-42 Connecting the outdoor unit on/off signal cable (dry contact connection) Step 3 Secure the cable to the right post of the cabinet using cable ties.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Place the sheet metal of the water sensor upwards and its detection board downwards on the ground. Figure 3-43 Connecting a cable to the water sensor ----End 3.11.2.3 (Optional) Installing the Differential Pressure Sensor...
Page 80
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-44 Securing a differential pressure sensor Step 2 Connect a pressure inlet tube to the + mark on the micro differential pressure sensor and route it to the cold aisle through the hole on the top of the cabinet.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide ----End 3.11.3 Teamwork Networking and Monitoring 3.11.3.1 Main Control Module Ports for the teamwork and monitoring network cables are on the main control module at the rear of the air conditioner.
Page 82
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-47 Pin sequence of network cable Step 2 Connect one end of the FE network cable to an FE_2 port in Figure 3-46, and connect the...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-49 Connecting the CAN teamwork cable ----End 3.11.3.3 Connecting the Monitoring Network Cable Connecting the FE Monitoring Network Cable (SNMP/Modbus-TCP) When the FE teamwork networking is used inside the air conditioners, connect the external monitoring network cable to the FE port on the air conditioner.
Page 84
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Connecting the RS485 Monitoring Network Cable (Modbus-RTU) When the CAN teamwork networking is used inside the air conditioners, connect the external monitoring network cable to the RS485 port on the air conditioner. To use the northbound RS485 monitoring, the communications protocol should be Modbus-TCP.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-51 Connecting the RS485 monitoring ----End 3.11.4 Connecting the T/H Sensor Outside the Cabinet Context T/H sensors outside the cabinet are configured to detect the temperatures of cold/hot aisles.
Page 86
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Figure 3-52 Cables routed outside the cabinet The T/H sensors inside the cabinet are secured at the return air side and their IN ports are connected to the main control board.
Page 87
Hot-aisle 5 temp/humid The default addresses of T/H sensors purchased from Huawei are 1. Keep the last RS485_R toggle switch at OFF. After the addresses are set, power on the device. On the display's home screen, choose Settings >...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide 3.12 Connections Verification After the installation, check the items listed in Table 3-14, Table 3-15, and Table 3-16, and record the check results. Table 3-14 Check items on the indoor unit...
Page 89
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 3 Installation Guide Check Item Expected Result Actual Result □ Passed □ Failed Differential The cable ties on the differential pressure tubes pressure switch are secured. □ Passed □ Failed There is no foreign matter in the differential pressure tubes.
Commissioning 4.1 Vacuumizing and Precharging Refrigerant Ensure that no combustion-supporting materials (air or additives) enter the air conditioning system during commissioning. Huawei shall not be liable for any risks and losses thus incurred. 4.1.1 Refrigerant Charge Amount Refrigerant R410A from name brands such as DuPont, Daikin, and Honeywell is recommended.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning 4.1.2 Vacuumizing Prerequisites Before vacuumizing the cooling system, ensure that the refrigerant pipes have passed the air tightness test and do not leak. Before vacuumizing the cooling system, ensure that all connectors are secured.
Page 92
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning If a low-temperature component is installed on the outdoor side, connect the pressure gauge and vacuum pump at the low-pressure, discharge pipe, and liquid pipe needle...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning If the precision of the pressure gauge is too low to display 60 Pa (absolute pressure), ensure that the pressure gauge pointer stays at the minimum scale while vacuumizing the cooling system. Preserve the pressure for 1 hour, and make sure the displayed pressure does not increase obviously.
Page 94
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-3 Precharging refrigerant into the system without a low-temperature component (1) Refrigerant cylinder (2) Electronic scale (3) Pressure gauge (4) Connection nut (5) Low-pressure needle valve...
Page 95
If the R410A refrigerant is provided by Huawei, put the refrigerant steel vessel upside down when charging in the refrigerant. If the refrigerant is not provided by Huawei, check with the refrigerant provider whether the steel vessel has a siphon. If the vessel has a siphon, do not put it upside down when charging refrigerant.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Do not move the pipe or steel vessel when charging refrigerant. Otherwise, the value on the electronic scale is influenced. When charging refrigerant for a cooling system without a low-temperature component, open only the low-pressure gauge valve.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Step 6 If teamwork networking is required, verify that the teamwork cable is correctly connected. Step 7 Verify that the cable connections and DIP switch settings of the T/H sensors are correct.
Page 98
To prevent the effect of misoperation on the system, log in as the operator user first before modifying parameters. Confirm with Huawei before modifying parameters that cannot be modified by operator users; otherwise, Huawei will not be liable for any consequences of the unauthorized modification.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-7 Compressor preheating warning If you need to query the remaining preheating time, choose Running > Device Details > Compressor on the home screen. Figure 4-8 Remaining compressor preheating time 4.4 Home Screen...
Page 100
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-9 Home screen Table 4-2 Note for the page Items Note Permission status indicates that you have not logged in to the system. indicates that you have logged in to the system as an operator user.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Items Note an alarm is generated. The current critical alarm refers to the current critical alarm and their and their quantity quantity. The current major alarm refers to the current major alarm and their and their quantity quantity.
Page 102
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-10 Common settings Step 2 Set the parameters by referring to Table 4-3. You are not recommended to modify the parameters not listed in Table 4-3.
Page 103
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Parameter Description Configuration Principle recommended Ctrl humid After the T/H control type and Set this parameter as required.40%–60% setpoint at the humidity value under this RH recommended...
Page 104
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Parameter Description Configuration Principle set point. Dehumid The dehumidification can be Enable indicates that the set to Enable, Disable, or dehumidification function will be Enabled when active pwr...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning 4.5.2 Temperature and Humidity Values Procedure Step 1 On the home screen, choose Settings > System Settings > T/H Sensor. Figure 4-11 displayed. Figure 4-11 Setting temperature and humidity values...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Parameter Description Configuration Principle mode temperature inside the room or temperature is to be controlled based aisles based on the Average, on the averaged data value collected Maximum, or Minimum of by the collector.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Step 2 Set Indoor fan ctrl type to Pressure diff control. Step 3 Change the other parameters based on the following instructions. Table 4-5 Parameter description Parameter...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-12 Setting the IP address, subnet mask, and gateway address Step 2 Set the parameters by referring to Table 4-6. Table 4-6 IP address settings Parameter...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-13 Setting WiFi parameters Step 2 Set the parameters by referring to Table 4-7. Table 4-7 WiFi settings Parameter Setting Method WiFi SSID Set WiFi SSID based on the actual configuration; WiFi SSID is the name used for the WiFi hotspot over which a mobile phone can connect to the air conditioner.
Page 110
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-14 Setting Modbus Setting Parameters for Modbus RTU Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings. Figure 4-14 displayed. Step 2 Set parameters for Modbus RTU by following instructions in Table 4-8.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Parameter Setting Setting Method a client, can connect to a remote server and establish communication. If you set Link mode to Server and client, the air conditioner, as a server, supports two client connection and establishes communication.
Page 112
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-15 Setting SNMP communications parameters Step 2 Set SNMP Version based on site requirements, and then tap Submit. If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read Community and...
Page 113
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-17 Setting write community Step 4 Add an SNMPv3 user. Tap Add under SNMP V3. Enter a planned value for User Name, select values for Auth. Protocol and Prop.
Page 114
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-19 Setting an SHA password Set AES Password and Confirm Password as planned, and tap , as shown in Figure 4-20. Figure 4-20 Setting an AES password Tap Submit.
Page 115
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning SNMP Port is set to 161 by default. Step 6 Tap Next Page. Step 7 Set SNMP trap parameters. Tap Add under SNMP Trap. Set Trap Address as planned and Trap Port to the actual port number.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-23 Exporting the MIB file successfully 4.5.8 Setting Teamwork Control Parameters Prerequisites Assign teamwork group number and teamwork unit address for the teamwork controlled precision air conditioners as follows: ...
Page 117
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-24 Teamwork settings Step 2 Set teamwork control parameters. All teamwork control parameters can be set on the master air conditioner. Only Teamwork group no., Teamwork unit address, Teamwork CAN resistor enable, Teamwork function and Network can be set on slave air conditioners.
Page 118
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Default Parameter Description Configuration Principle Value function is enabled, this device works in harmony with others that in the same group. Teamwork Set the teamwork mode. The...
Page 119
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Default Parameter Description Configuration Principle Value recalculated. Requiremen Enable or disable the Avoid competit run is Disable t control requirement control for the recommended for the master device.
Page 120
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Step 4 On the home screen of any teamwork controlled air conditioner, tap . If the teamwork control succeeds, the teamwork topology of the air conditioner in the group is displayed, as...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Parameters Note color: red, bright gray as shown in Bright gray indicates that the device is operating without any critical alarms, as shown in If teamwork succeeds, the teamwork icon is green. If teamwork fails, the teamwork icon is red. If teamwork mode is disabled, the teamwork icon is gray.
Page 122
(EMS) is effective only when the remote dry contact or On/Off status on remote is on the status of on. Prerequisites Download the Service Expert app from Huawei app store and runs on Android. Step 1 Tap Start on the home screen of the ACC. ...
Page 123
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-28 Startup Step 2 Open the Service Expert app. User interfaces displayed in this document correspond to the APP software version V100R001C00B043T007 and are for reference only.
Page 125
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-30 Generating a startup password Step 6 On the Offline Activation screen, enter Bar code and Verification code, which are available on the home screen of the ACC shown in Figure 4-26.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning 4.7 Charging the Remaining Refrigerant Prerequisites Check that the outdoor unit switch is turned on before you start the compressor. Remove the refrigerant steel vessel after checking that no more refrigerant is required.
Page 127
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Context The startup wizard allows for commissioning of components such as the indoor fan, electric heater, humidifier, condensate pump, and cooling system. It also supports component automatic operation and automatic device checking, and can output commissioning report.
Page 128
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-32 Checking before startup Step 3 Tap Yes for check items one by one according to the prompt messages on the screen. Step 4 Tap Yes and enter the screen where you select commissioning items, as shown in Figure 4-33.
Page 129
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-34 Fan commissioning The fan commissioning item is mandatory. After commissioning a component succeeds, the system automatically performs commissioning for the next component you selected. If commissioning fails, startup wizard ends.
Page 130
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-35 L1/L2/L3 current detection Figure 4-36 Electric heater commissioning Step 7 After the electric heater commissioning, the humidifier commissioning screen is displayed. Verify that the main water inlet valve is open. Check whether the humidifier pipes and the solenoid valve leak.
Page 131
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-37 Humidifier commissioning Step 8 After the humidifier commissioning, the condensate pump commissioning screen is displayed. Check whether the condensate pump vibrates and generates operating sound.
Page 132
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-39 Cooling system commissioning Step 10 View the commissioning result. Figure 4-40 is displayed if component commissioning succeeds. Figure 4-40 Commissioning successfully Figure 4-41 is displayed if component commissioning fails, which ends startup wizard commissioning.
Page 133
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning If commissioning fails, tap Commissioning failed. in Figure 4-41 to view the details, as shown in Figure 4-42. After the fault is cleared, choose Maint > Wizard Startup to enter the wizard startup screen for new commissioning.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-43 Adjusting the air deflecting assembly Put down the button. 4.9 (Optional) Power-off Context In shutdown mode, the Shutdown button is green (unavailable) and the Start button is gray (available).
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 4 Commissioning Figure 4-44 Shutdown Step 2 Tap Yes. If the device is successfully shut, the system displays a message, indicating that the command is successfully triggered. Step 3 Turn off the switch QF3 that controls the outdoor unit and compressor and switch QF4 that controls the electric heater.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Operation and Maintenance 5.1 Routine Maintenance 5.1.1 Data Record Before performing monthly maintenance, record data in Table 5-1. Table 5-1 Recording table Menu Item Parameter Record Choose Settings >...
Page 137
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Table 5-2 Monthly maintenance checklist Task Baseline Requirement Troubleshooting The air filter is clean and not Replace the air filter. It is recommended filter blocked.
Page 138
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Task Baseline Requirement Troubleshooting and then charge new refrigerant. NOTE If the sight glass does not obviously turn green, use a blow drier to blow wind to the filter until the sight glass is green.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-1 Removing a water pan filter 5.1.3 Quarterly Maintenance Table 5-3 lists quarterly maintenance items for the indoor unit. Table 5-3 Quarterly maintenance checklist...
Calculate the total cooling capacity and total server load of running indoor units. If the total load exceeds 80% of the total cooling capacity of the air conditioner, Huawei recommends increasing the number of air conditioners.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance 5.2 Alarm Reference Table 5-5 describes the alarm reference of the NetCol5000-A. If the Clear icon is displayed on the Details screen, the alarm can be manually cleared by tapping the Clear button after the fault is rectified.
Page 142
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 2 T/H brd sensor are loose or T/H sensor. comm generated. damaged. 2. Set the DIP switch of the failed 2.
Page 143
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity or is unavailable. outdoor unit. 7. Cables to the outdoor unit 8. Maintain or replace the are not properly outdoor unit or unit connected.
Page 144
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity switch is blocked or 5. Check the cables to the disconnected. differential press switch. 5. The cables to the differential press switch are loose or damaged.
Page 145
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 1. The power supply voltage 1. Check the power supply a033 Power Major The alarm is too low.
Page 146
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity overflow and the connected. connection to the system overflow sensor. 3. The water sensor is shuts faulty.
Page 147
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 1. The load is low. 1. Please consult Huawei a049 Supply-air Warning The alarm technical support. 2. The ambient temp is low.
Page 148
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity PSU 2 generated. fault 1. The communication 1. Check the a054 PSU 1 Major The alarm cables of the PSU are...
Page 149
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 1. The refrigerant leaks. 1. Identify and repair the a060 Comp Major The alarm leaking point, and refill suction LP 2.
Page 150
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity overvolt generated. 2. The comp driver is faulty. comp driver. 3. The comp is faulty. 3. Maintain or replace the comp.
Page 151
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity dirty/blocked & heat ex module. effect poor. 5. The drive module is faulty. 1. The cables to phase U of 1.
Page 152
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity abnormal float are loose or high float. generated. damaged. 2. Maintain or replace the 2. The high float is faulty or high float or clear the stuck.
Page 153
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 1. The cables to the indoor 1. Check the cables to the a102 Indoor fan Major The alarm fan are loose or damaged.
Page 154
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity ation fault generated. 2. The ETH converter is works properly. faulty. 2. Maintain or replace the 3. The smart socket is ETH converter.
Page 155
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity abnormal incorrect for slave units. fan. L1/L2 generated. 2. Teamwork settings are 2. Modify teamwork disconnect incorrect for the master settings for slave units to unit.
Page 156
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity and the sensor is faulty. 2. Verify that the suction compresso temperature sensor works r shuts properly.
Page 157
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity open generated. the lower threshold. voltage meets specifications. 1. A cable of the fan is loose 1. Secure the cables...
Page 158
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 3. The fan is faulty. a145 handling methods. 2. Cut off the three-phase power supply and check whether the driver output cable is faulty.
Page 159
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity a167 Auxiliary Major The alarm The auxiliary power supply Replace the auxiliary power power is faulty. supply module.
Page 160
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity 3. The aisle T/H sensor of unit, and monitoring host an air conditioner is (ECC). faulty. 3. Maintain or replace the 4.
Page 161
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity experiences overvoltage. humidifier pump voltage. 5. The water pump races 5. Rectify the liquid level due to a liquid level detection fault.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Alarm Alarm Alarm Impact Possible Cause Solution Severity down. board. 1. The PSU is faulty. 1. Replace the PSU. a222 Main ctrl Critical The alarm module 2.
Page 163
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Symptom Possible Cause Solution start. the display. The compressor does not work. Check whether the drive is faulty. Replace it if it is faulty. The refrigerant loop or a...
Page 164
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Symptom Possible Cause Solution generates normal range. excessive Refrigerant oil is insufficient. Add refrigerant oil. noises. The transport sheet metal is not Remove the sheet metal.
Page 165
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Symptom Possible Cause Solution The liquid level detector is faulty. Check the alarm. Check cable connections for high and low liquid level detectors. Check whether the liquid level detectors are damaged.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Symptom Possible Cause Solution heater does heater are short-circuited. not stop heating. If the fault persists, contact Huawei technical support. 5.4 Parts Replacement After replacing any part, verify that the new part works properly.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-2 Removing an air filter Step 2 Draw out the air filter. Step 3 Remove the lower air filter in the same way. Step 4 Install new air filters in an inverse order.
Page 168
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance A spare indoor fan of the same model is available and functional. Tools: protective gloves, Phillips screwdriver, diagonal pliers, cable tie Context The indoor fan can be maintained only from the front door. Replacing fan 9 is used as an example.
Page 169
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-5 Installing a new fan Step 4 Switch on the circuit breaker for the faulty fan 9, and close the front door. Figure 5-6 Switching on the circuit breaker for the faulty fan 9 Step 5 Power on the device.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-7 Performance maintenance Step 6 Tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms. ----End 5.4.3 Replacing the Differential Pressure Switch Prerequisites ...
Page 171
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-8 Removing a differential pressure switch Step 4 Use a Phillips screwdriver to remove the screws on the top cover of the differential pressure...
Page 172
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-9 Setting values for a differential pressure switch Step 7 Install the new differential pressure switch and the pressure tube, and connect the cables.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 9 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms. ----End 5.4.4 Replacing the Compressor...
Page 174
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-11 Angle valve (1) Angle valve nut (2) Adjustable nut (3) Pipe nut Procedure Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the PDC.
Page 175
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-12 Removing the electric heating belt and compressor power cables Step 6 Remove the compressor. Heat the air intake angle valve joints using a heat gun for 10 minutes. Secure the angle...
Page 176
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-13 Removing a compressor angle valve After removing the valve, seal the suction vent immediately to ensure that the system is clean and moisture does not enter the pipe.
Page 177
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-14 Removing a compressor bracket Step 7 Secure the new compressor to the bracket again using a solid wrench. Figure 5-15 Installing a compressor bracket...
Page 178
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Seal the screw thread joints in the pipe using sealant. After the installation, check that the input power cables of the compressor are in the same phase sequence as the wiring terminals.
Page 179
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-17 Connecting cables to the electric heating belt and the compressor Step 11 Vacuumize the system and precharge refrigerant, as shown in 4.1 Vacuumizing and Precharging Refrigerant.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance ----End 5.4.5 Replacing the Filter Dryer Prerequisites The filter dryer needs to be replaced. A spare filter dryer of the same model is available and functional.
Page 181
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Exercise caution because the device is still energized after it is shut down on the controller home screen. Step 2 Open the rear door and remove the air filter.
Page 182
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 5 Remove the plastic plug from the port of the new filter dryer. Step 6 Install the new filter dryer, as shown in Figure 5-21.
Tools: Phillips screwdriver, diagonal pliers, cable tie. Before checking and maintaining the NetCol5000-A, ensure that the primary power supply to the NetCol5000-A is disconnected and the drive has been placed without primary power supply for 10 minutes. Otherwise, electric shocks may occur.
Page 184
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-22 Removing cables Step 4 Remove the four screws on the driver using a Phillips screwdriver and pull out the driver, as shown in Figure 5-23.
Page 185
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 5 Install the new driver. Figure 5-24 Installing a driver Step 6 Connect the new driver cables. Issue 01 (2017-07-27) Huawei Proprietary and Confidential...
Step 7 Install the air filter and close the rear door. Step 8 Power on the NetCol5000-A, choose Maint > Diagnostic Mode > Enter on the home page, start the compressor, and check that the compressor works properly and the NetCol5000-A generates no alarms.
Page 187
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-26 Liquid level detector (1) High liquid level detector (2) Low liquid level detector Procedure Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the PDC.
Page 188
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-27 Removing a water pan cover Step 3 Cut the cable tie securing the liquid level detector and remove the terminal. Step 4 Remove the two butterfly nuts on the liquid level detector fastener, remove cables from the...
Page 189
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 5 Remove the liquid level detector, as shown in Figure 5-29. Remove screws from the high liquid level detector using a Phillips screwdriver, and remove the high liquid level detector.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-30 Installing a liquid level detector Step 7 Install the water pan cover, and close the front door. Step 8 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms.
Page 191
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Procedure Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the PDC. Exercise caution because the device is still energized after it is shut down on the controller home screen.
Page 192
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-32 Removing a condensate pump assembly Remove the hose clamp at the water pan drain outlet, and remove the hose, as shown by (1) and (2) in Figure 5-32.
Page 193
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 5 Install the new condensate pump and reinstall the condensate pump assembly in the cabinet. Connect the water pipe and secure it using hose clamps. Connect the condensate pump power cable.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance 5.4.9 Replacing the Humidifier Pump Prerequisites The humidifier pump needs to be replaced. A spare humidifier pump of the same model is available and functional.
Page 195
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-36 Removing a humidifier pump Step 6 Install the new humidifier pump by performing the preceding steps in reverse order, connect the hoses and cables, and secure them using hose clamps.
Page 196
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-37 Installing a humidifier pump Step 7 Install the air filter and close the rear door. Step 8 Power on the device. On the LCD home screen, choose Maint > Performance Maint, and clear the humidifier pump runtime.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance 5.4.10 Replacing the Wet Film Humidifier Prerequisites The wet film humidifier needs to be replaced. A spare wet film humidifier of the same model is available and functional.
Page 198
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-39 Removing a wet film humidifier Hold the blue release sleeve and remove the water inlet pipe. Loosen the two captive nuts on one side of the wet film humidifier and remove the humidifier.
Page 199
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-40 Install a wet film humidifier Put the bottom of wet film humidifier into the installation position, and then put the top into the installation position.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance 5.4.11 Replacing the Electric Heater Prerequisites The electric heater needs to be replaced. A spare electric heater of the same model is available and functional.
Page 201
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-43 Removing an electric heater Step 5 Install the new electric heater in the reverse order of the removal. Issue 01 (2017-07-27) Huawei Proprietary and Confidential...
Page 203
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-45 Installing a fan support Install the fan support by following the consequence on the label of fan support, to avoid reverse installation. Step 7 Power on the system. On the main screen, choose Maint > Diagnostic Mode > Enter.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance ----End 5.4.12 Replacing a Strong-current Box Prerequisites A component inside the electric control box, such as the main control board, circuit breaker, AC contactor, fuse, or fuse base, needs to be replaced.
Page 205
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-47 Removing cables Step 4 Remove the four screws in front of the strong-current box using a Phillips screwdriver, as shown in Figure 5-48.
Page 206
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-48 Removing a strong-current box Step 5 Replace the electric control box. Ensure that the four screws are tightened when installing the strong-current box.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-49 Installing a strong-current box Step 7 Reconnect the cables and terminals shown in Figure 5-47. Step 8 Install the air filter and close the rear door.
Page 208
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance The new module must be installed in the same slot as the faulty module. Otherwise, the air conditioner may fail to work properly. ...
Page 209
When installing a new module, ensure that the handle is in the upper part of the module, and the HUAWEI logo is in the lower left corner of the module. Step 5 Insert the spare module into the corresponding slot, and flip the clip upwards to lock the module.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-52 Locking a module Step 6 Install the network cable and air filter, and close the rear door. Step 7 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms.
Page 211
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 3 Disconnect cables from the RS485_IN and RS485_OUT ports on the T/H sensor, as shown by (1) in Figure 5-53. Step 4 Pull out the T/H sensor in the direction shown by (2) in Figure 5-53.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-54 Installing a T/H sensor Step 6 Install the air filter and close the rear door. Step 7 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms.
Page 213
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Exercise caution because the NetCol5000-A is still energized when it is being shut down on the LCD. Step 2 Open the front door and disconnect cables. Figure 5-55 Disconnecting cables...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 6 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms. ----End 5.4.16 Replacing the Switch...
Page 217
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-59 Removing a faulty switch Step 4 Remove all cables from the faulty switch QF3 or QF4, as shown by (2) in Figure 5-59.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-60 Installing a switch Step 7 Reconnect the cables to the switch and reinstall the cover, as shown by (2) and (3) in Figure 5-60.
Page 219
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Exercise caution because the device is still energized after it is shut down on the controller home screen. Step 2 Open the rear door and remove the air filter.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-62 Installing a new contactor Step 7 Install the air filter and close the rear door. Step 8 Power on the device and tap Startup on the home screen. Ensure that the air conditioner is running normally without any alarms.
Page 221
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Exercise caution because the device is still energized after it is shut down on the controller home screen. Step 2 Open the rear door and remove the air filter.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-64 Installing an SPD Step 7 Reinstall the strong-current box, as shown by Step 6 Step 7 5.4.12 Replacing a Strong-current Box. Step 8 Power on the device, and ensure that the air conditioner works properly without alarms.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-66 Installing a relay Step 5 Power on the device, and ensure that the air conditioner works properly without alarms. Step 6 Install the air filter and close the rear door.
Page 225
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Step 2 Open the rear door and remove the air filter. Step 3 Find the fuse to be replaced and open the knife-shaped fuse holder. Take the fuse out of the fuse holder by using a flat-head screwdriver.
Page 226
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 5 Operation and Maintenance Figure 5-68 Replacing the fuse Step 5 Power on the device, and ensure that the air conditioner works properly without alarms. Step 6 Install the air filter and close the rear door.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.1 Querying Temperature and Humidity Curves Context The T/H Curve screen displays temperature and humidity curves showing the recent temperature and humidity changes. You can choose to display the curves showing data changes of recent one hour, one day, seven days, or 30 days.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ You can view the humidity from (humidity set point - 5%) to (humidity set point + 5%) at least, and from (humidity set point - 50%) to (humidity set point + 50%) at most. Specific humidity fluctuation range displayed varies according to different models of precision air conditioners.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ If the icon is not displayed on the Details screen, the alarm can be automatically cleared after the fault is rectified. If the icon is displayed on the Details screen, it indicates that the alarm can be cleared manually.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Enter the Device Details screen and then enter the menu of a specific component. All parameters for the component are displayed. Procedure When viewing the component status through Status, choose Common Functions >...
Page 232
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Enter the Operating Info screen that displays the major system parameters such as the current detected temperature, humidity, dew point temp, and auxiliary power voltage. ...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.7 Querying Version Details Procedure Step 1 On the home screen, select About. Step 2 On the About screen, tap Version Info or E-label. Figure 6-11 Figure 6-12 are displayed.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.8 Deleting Historical Alarms Context To delete historical alarms, log in as the admin user. Exercise caution when deleting all historical alarms. Because this operation may cause clearance of all historical alarms and affects device maintenance.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ If you perform this operation, all logs will be deleted, and device maintenance will be affected. Exercise caution when doing this operation. Procedure Step 1 On the home screen, choose Maint > Log Maint > Delete Logs > Yes to delete all the logs.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-14 Select path Step 2 Tap the file where the user saves current data in the Select Path dialog box and tap Next. Then tap Yes in the displayed dialog box.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Procedure Step 1 On the home screen, choose Maint > Performance Maint. Figure 6-16 is displayed. Figure 6-16 Performance Maint screen Step 2 Tap Clear of a specific performance parameter to clear its runtime.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ ----End 6.13 Calibrating the Screen Context You can calibrate for touching point deviation on the touchscreen. You can calibrate the screen by tapping the screen on the Screen Calib page or by DIP switch.
Page 239
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-19 Screen displayed when the calibration is complete Calibrating the screen by DIP switch. Flip toggle switch 1 for the display to ON, and others to the opposite position, and wait for 3 seconds before calibrating.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.14 How to Perform Quick Settings Context On the quick settings screen, you can set the language, time, date, and system. Procedure Step 1 Choose Settings > Quick Settings on the home screen. The quick settings screen is displayed,...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.16 How to Modify a Password Prerequisites To modify a password, log in as the admin user or operator user. You can only modify the password of the current user.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-23 Modifying the password If you forget the password, restore the initial password by referring to 6.17 Restoring Factory Settings. ----End 6.17 Restoring Factory Settings Context If you have forgotten the password or need to delete system information, you can restore factory settings using DIP switch on the main control module.
Page 243
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ If you restore factory settings, all system data will be restored to the state before delivery, including login passwords, operation logs, parameter configurations, alarms, and performance statistics. Perform this operation with caution as it may affect other users.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ After the system is restored to factory settings, the user password is also reset to the preset password, and must be promptly modified to ensure information security and normal system running.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ ----End 6.20 How to View Teamwork Control Information Procedure Step 1 On the home screen, choose > . The teamwork control information is displayed, as shown in Figure 6-26.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ All parameters displayed on Settings > Comm Settings. Date format and time zone settings displayed on Settings > User Settings. All parameters displayed on Maint > Sensor Adjust.
Page 247
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-27 Entering the user name and password The new password should meet the following requirements: Contains at least eight characters. Contains at least two types of characters: lowercase letter, uppercase letter, digit, space, and special character (`~!@#$%^&*()-_=+\|[{}];:'",<.>/?).
Page 248
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-28 Switching to the root user Step 4 Enter passwd (the password change command) to change the password. In the displayed window, enter a new password and confirm it, as shown in Figure 6-29.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.23 How to Import a Certificate and a Key Prerequisites You have obtained CA certificate file, local certificate file, and key file into a USB disk that...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ 6.24 How to Import a Configuration file Context You are advised to use the FAT32 USB flash drive with a capacity no greater than 64 GB. Procedure Step 1 Tap Maint >...
Page 251
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual 6 FAQ Figure 6-33 Data process 1 Figure 6-34 Data process 2 Step 4 After the file is imported successfully, Figure 6-35 is displayed. Then tap Finish. Figure 6-35 Importing the file successfully If the file fails to be imported, a failure message will be displayed.
Page 253
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual A Electric Control Box Layout Table A-1 Electric control box layout description Name and Function Side (1) Dual (2) Dual (3) Crankcase (4) Electric heater contactor view power power...
Page 254
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual A Electric Control Box Layout Name and Function DPT 5 V DC (Reserved) Reserved Fan circuit breakers Fan1–Fan10 (between the two groups of fans on the front door) Front...
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Parameter Description Parameters and preset values are from ACC V200R001C30B078. Parameters are those that can be queried by the admin user. Table C-1, only the component names are used. For example, Indoor fan 1 and Indoor fan 2 are indicated by Indoor fan.
Page 257
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value Settings > IP assigning mode Specifies the way of allocating IP addresses Manual for precision air conditioners. Comm Settings > IP...
Page 258
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value set to Client. Network port It is recommended that you retain the default 16100 value 16100. If you need to change the value, enter a value as required.
Page 259
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value power is active and the ambient temperature is lower than the certain temperature range of the temperature set point. Heat mode...
Page 260
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value ports 1 and 2 for reporting common alarms are open and generate no alarms. Outdoor fan Select the control mode for the outdoor fan...
Page 261
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value main power is active and the ambient humidity is lower than the certain humidity range of the humidity set point. Humid mode Specifies the starting mode of the humidifier.
Page 262
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value at ctrl point device conducts cooling or heating based on the settings. Ctrl humid After the T/H control type and the humidity 25.0% RH...
Page 263
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual C Parameter Description Menu Parameter Description Default Value Time zone Specifies the time zone displayed on the Consistent with the ACC. current interface time zone Maint > Compressor total Total runtime for each component.
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual E Acronyms and Abbreviations Acronyms and Abbreviations alternating current Computational Fluid Dynamics Controller Area Network direct current dual in-line package electronic commutation electronic expansion valve Element Management System liquid crystal display...
Page 269
NetCol5000-A 42 kW Air Cooled In-row Precision Air Conditioner User Manual E Acronyms and Abbreviations negative temperature coefficient power distribution cabinet positive temperature coefficient Power Usage Effectiveness RCCB Residual Current Circuit Breaker surge protective device thin film transistor Universal Series Bus...