NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 3-14 Removing the transport fasteners from the compressor
Step 2 Remove the transport fasteners.
Step 3 Tighten the bolts on the compressor again to a torque of 12 N•m.
----End
3.6 Install Process
Figure 3-15
Issue 01 (2017-07-27)
Do not remove the bolts directly.
Put away the removed transport fasteners so that you can reinstall them if the indoor unit is to be
transported again in the container scenario.
shows the process for installing an indoor unit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
40