Huawei NetCol5000-A User Manual page 52

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Do not remove the anchor bolts. Otherwise, rework is required if the cabinet height does
not meet requirements.
Anchor bolt adjustment method: Rotate anchor bolts clockwise to raise the cabinet and
rotate them counterclockwise to lower the cabinet. Anchor bolts can be adjusted within a
range of 0–8 mm.
Levelness check standard: Ensure that the cabinet is level in width and depth directions
when leveling the cabinet. Put a level at the bottom of the cabinet in width and depth
directions and check that the air bubble is in the middle between the two lines marked on
the glass tube, as shown in
Figure 3-18 Leveling a cabinet
(1) Level
Step 5 (Optional) Combine the cabinets, as shown in
1.
2.
3.
Issue 01 (2017-07-27)
Remove the M5 tapping screws that secure the connecting kit and then remove the
connecting kit.
Remove the M4 screw assembly from the position for combining cabinets.
Combine the adjacent cabinets by installing the connecting kit and M4 screw assembly at
the combination positions on the front and rear doors of the cabinets.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
3-18.
Figure
3-19.
3 Installation Guide