5.2 Alarm Reference

Table 5-5
If the Clear icon is displayed on the Details screen, the alarm can be manually cleared by
tapping the Clear button after the fault is rectified. The alarm clearance type (automatic or
manual) varies with precision air conditioners. Alarms can be cleared are a009, a013, a025,
a046, a058, a061, a062, a064, a079, a095, a130, a137, a179, a182, a190.
Table 5-5 Alarm description
Alarm
Alarm
ID
a001
Return-air
1 temp
invalid
Return-air
2 temp
invalid
Return-air
a002
HT
a003
Return air
LT
a004
Return-air
2 humid
invalid
a007
Return-air
Issue 01 (2017-07-27)
describes the alarm reference of the NetCol5000-A.
Alarm
Impact
Severity
Major
The alarm
is
generated.
The alarm
Critical
is
generated.
Warning
The alarm
is
generated.
Major
The alarm
is
generated.
Major
The alarm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The cables to the T/H
sensor are loose or
damaged
2. The T/H sensor is faulty.
1. The load is high or the
refrigeration capacity is
insufficient.
2. The ambient temp is
high.
3. The return-air HT alarm
threshold is
inappropriate.
4. The temp displayed is
different from the actual
temp.
1. The load is low.
2. The ambient temp is low.
3. The return-air LT alarm
threshold is
inappropriate.
4. The temp displayed is
different from the actual
temp.
1. The cables to the T/H
sensor are loose or
damaged.
2. The T/H sensor is faulty.
1. The cables to the T/H
5 Operation and Maintenance
Solution
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
1. Add more air conditioner
units or Consult
Huawei technical
support.
2. Check other causes if the
alarm persists after
startup.
3. Adjust the return-air HT
alarm threshold.
4. Calibrate or replace the
abnormal sensors.
1. Please consult Huawei
technical support.
2. Check other causes if the
alarm persists after
startup.
3. Adjust the
undertemperature alarm
threshold.
4. Calibrate or replace the
abnormal sensors.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
1. Check the cables to the
133