Huawei NetCol5000-A User Manual page 65

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
threads: G 1/2 inch, delivered with
the water inlet pipe for the air
conditioner
(4) Pagoda connector: G 1/2 inch;
connected to a pagoda connector
with outer screw threads
Bottom Pipe Routing
Step 1 Straighten the water inlet pipe delivered with the air conditioner, and route it from the inside
to the outside through the water inlet hole at the bottom of the air conditioner.
Figure 3-31 Downward routing of the water inlet pipe
Step 2 Connect the external water inlet pipe based on the actual condition and wrap the pipe with
thermal insulation foam.
----End
Issue 01 (2017-07-27)
The object shown in the dotted line box is the water inlet pipe connector with inner screw threads
delivered with air conditioners. The hose clamp as shown by (5) in the preceding figure is provided in
standard configuration. Other parts are not provided and need to be purchased.
The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a
hose or rigid pipe based on site requirements.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
adapter: G 1/2 inch; connected
to a rigid pipe with outer screw
threads
(5) Hose clamp
3 Installation Guide
made of PP-R or
other materials
(6) Hose: made of
EPDM or other
materials
57