NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 3-12 Positions of the needle valves
(1) Low-pressure needle
valve
----End
3.5 Removing the Transport Fixing Sheet Metals
3.5.1 Removing the Pallet
Procedure
Step 1 Use a 10# socket wrench to remove the eight M6x16 screws securing the fasteners to the
cabinet, and use an 18# socket wrench to remove the four M12x35 screws securing the
fasteners to the pallet, as shown in
Issue 01 (2017-07-27)
(2) Discharge pipe needle
valve
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3-13.
3 Installation Guide
(3) Liquid pipe needle
valve
38