Huawei NetCol5000-A User Manual page 260

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Menu
Parameter
Outdoor fan
control mode
Cooling
Settings >
Units start time
System
integral
Settings >
Disallow on/off
System Control
via EMS
Silent mode
Cooling
Heat
Heat mode
Humid
Issue 01 (2017-07-27)
Description
ports 1 and 2 for reporting common alarms
are open and generate no alarms.
Select the control mode for the outdoor fan
based on the cable connection of the indoor
and outdoor units (dry contact cable or RS485
cable).
The cooling function can be set to Enable or
Enabled when active pwr
Specifies the time interval between the starts
of units under teamwork control.
When the function is disallowed, the EMS is
not allowed to turn on or off the devices.
When the silent mode is enabled, the indoor
unit is running in low noise mode. When the
silent mode is disabled, the indoor unit is
running in normal mode.
The cooling function can be set to Enable or
Enabled when active pwr
Enable indicates that the electric heater will
be started when the ambient temperature is
lower than the certain temperature range of
the temperature set point. Disable indicates
that the electric heater will not be started.
Enabled when active pwr indicates that the
electric heater will be started when the main
power is active and the ambient temperature
is lower than the certain temperature range of
the temperature set point.
If Dehumid heat is selected, the electric
heater starts heating based on the current
temperature only after the dehumidification
function is enabled. If Low-temp heat is
selected, the electric heater starts heating
based only on the current temperature, no
matter the dehumidification function is
enabled or not. If Dehumid & LT heat is
selected, the electric heater starts heating
when the dehumidification and heating
condition or the low temperature heating
condition is met.
Enable indicates that the electric humidifier
will be started when the ambient humidity is
lower than the certain humidity range of the
humidity set point. Disable indicates that the
electric humidifier will not be started.
Enabled when active pwr indicates that the
electric humidifier will be started when the
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
C Parameter Description
Default Value
Communicate
Enable
2s
No
Enable
Enable
Enable
Dehumid heat
Enable
252