42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Operating
temperature
Protection level
Installation
mode
Pipe and cable
routing
Altitude
Table 2-8 Derating coefficients
Altitude
(m)
Air volume
coefficient
Cooling
capacity
coefficient
The sensible heat ratio is all 100% in rated condition.
Issue 01 (2017-07-27)
Specifications
IP20
Floor or ESD floor-mounted
Pipes and cables routed from the top or bottom
0–4000 m. When the altitude exceeds 1000 m, the power should be
derated. For detailed derating data, see
0
1000
1500
1
0.887
0.835
1
0.940
0.909
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Table
2-8.
2000
2500
3000
0.785
0.737
0.692
0.878
0.846
0.815
2 Product Description
3500
4000
0.649
0.608
0.784
0.753