Huawei NetCol5000-A User Manual page 102

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 4-10 Common settings
Step 2 Set the parameters by referring to
You are not recommended to modify the parameters not listed in
Table 4-3 Parameter description
Parameter
T/H control
type
Ctrl temp
setpoint at
ctrl point
Issue 01 (2017-07-27)
Table
Description
Cold-aisle, Hot-aisle,
Return-air, or Supply-air can
be set as required. The
temperature and humidity set
points correspond to the
selected control type can be
set.
After the T/H control type and
the temperature value under
this type are set, the device
conducts cooling or heating
based on the settings.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4-3.
Table
Configuration Principle
Return-air: Select Return-air to
control the temperature and humidity
around the air return vent of the
precision air conditioner.
Supply-air: Select Supply-air to
control the temperature and humidity
around the air supply vent of the
precision air conditioner.
Cold-aisle: For a cold aisle, select
Cold-aisle to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
Hot-aisle: For a hot aisle, choose
Hot-aisle to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
Set this parameter as required.
Return air temperature: 26–35° C
recommended
Supply air temperature: 18–24° C
recommended
Cold aisle temperature: 18–24° C
recommended
Hot aisle temperature: 26–35° C
4 Commissioning