NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
Step 3 Use the wrench to adjust the feet by using a measuring tape and level, keep the feet touch the
ground after leveling.
Make sure the parallel mounting holes in the NetCol5000–C are aligned with those in the server
cabinets.
Step 4 Removing the four M10 bolts on the upper support.
Step 5 Align the tapped hole, and secure the NetCol5000-C onto the support by using bolts that
removed on
Figure 3-14 Securing the NetCol5000-C onto a support
----End
Issue 02 (2013-12-10)
Step
4, as shown in
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3-14.
3 Installation Guide