4.4 GOT Side Settings

4.4.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MODBUS
• Controller Type: MODBUS
• I/F: Interface to be used
• Driver: MODBUS/RTU
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

4.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be set and
confirmed in [I/F Communication Setting]. For details,
refer to the following.
1.1.2 I/F communication setting
4 - 8
4. MODBUS(R)/RTU CONNECTION

4.4 GOT Side Settings

Click!
[Controller Setting] from the
4.4.2
Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
Transmission
Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Host Address
*1
Delay Time
32bit Storage
FunctionCode[0F]
FunctionCode[10]
Coil read times
Input relay read
time
Holding register
read times
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address in the
network of the GOT.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the GOT.
(Default: 0ms)
Select the steps to store two words
(32-bit data).
(Default: LH Order)
Select the FunctionCode [0F].
(Default: Used)
Select the FunctionCode [10].
(Default: Used)
Set the Coil read time.
(Default: 2000)
Set the Input relay read time.
(Default: 2000)
Set the Holding register read times.
(Default: 125)
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
1 to 247
0 to 300ms
LH Order/HL
Order
Used/Unused
Used/Unused
1 to 2000
points
1 to 2000
points
1 to 125
points