Control Cable Ducts - ABB ACS800-02 Hardware Manual

Acs800-02 drives (45 to 500 kw); acs800-u2 drives (60 to 600 hp)
Hide thumbs Also See for ACS800-02:
Table of Contents

Advertisement

A diagram of the cable routing is below.
Input power cable
min 200 mm (8 in.)

Control cable ducts

Not allowed unless the 24 V cable is
insulated for 230 V or insulated with an
insulation sleeving for 230 V.
Drive
90 °
Control cables
24 V 230 V
Motor cable
min 300 mm (12 in.)
Power cable
Motor cable
min 500 mm (20 in.)
24 V
230 V
Lead 24 V and 230 V control cables in
separate ducts inside the cabinet.
Planning the electrical installation
41