Installation Procedure; Choose The Mounting Orientation (A, B, C Or D); Mounting Orientations A And B - ABB ACS800-02 Hardware Manual

Acs800-02 drives (45 to 500 kw); acs800-u2 drives (60 to 600 hp)
Hide thumbs Also See for ACS800-02:
Table of Contents

Advertisement

Installation procedure

Choose the mounting orientation (a, b, c or d)

a)
Symbols:
Frame
Mounting
Required free space around the unit for mounting, maintenance, service and cooling *
size
orientation
R7
a, d
b
c
R8
a, d
b
c
* space for the installer not included
** space for fan and capacitor replacement not included

Mounting orientations a and b

Make holes in the wall (recommended):
1. Lift the unit against the wall into the mounting place.
2. Mark the locations for the two fixing points in the wall (not for mounting orientation a if the unit is
subjected to sideways vibration).
3. Mark the bottom edges of the unit to the floor.
b)
Lifted from above
required free space
air inlet surface
wall fixing point (recommended)
control panel mounting slot
Front
mm
in.
500
20
-
-
-
-
600
24
-
-
-
-
c)
With enclosure extension
Note: The unit can also be installed away
from the wall.
Side
mm
in.
-
-
500
20
200**
7.9**
-
-
600
24
300**
12**
d)
Above
mm
in.
200
7.9
200
7.9
lifting space
lifting space
300
12
300
12
lifting space
lifting space
Installation
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-u2

Table of Contents