10
1
2
3
10
70
50
Earth wire
System interconnection wire
See the figure on the left for
connecting wires to the terminal
block.
Indoor / Outdoor connecting wire
 Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Terminal block for
remote controller
Terminal block
wiring of indoor unit
A
A
B
B
Remote controller wire
(Locally procured)
 Wiring on the ceiling panel
As per the Installation Manual of the ceiling panel,
connect the connector (2P: Red) of the ceiling panel to
the connector (5P: White) onto the P.C. board within
the electrical control box.
5P connector (White)
Cord clamp
Wire from ceiling panel
25-EN
Remote
controller
unit
– 13 –
8

Applicable controls

REQUIREMENT
• When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes approx. 5 minutes until the remote controller
becomes available.
Approx. 5 minutes
"SETTING"
"SETTING"
Power on
goes out
flashes
<When power is turned on for the second (or later)
time>
It takes approx. 1 minute until the remote controller
becomes available.
Approx. 1 minutes
"SETTING"
"SETTING"
Power on
goes out
flashes
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, sub remote controller,
or remote-controller-less system (for central
remote controller only). Therefore, install the
wired remote controller to change the settings.
 Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
Remote
controller is
If a CODE No. not listed is set, it may not be possible to
available
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT31E). (There are more CODE No.)
Remote
controller is
available
4
6
1
5
2
1
Push and hold
button and "TEMP."
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
• If the CODE No. is not [01], push
clear the display content, and repeat the
procedure from the beginning. (No operation of
the
remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor unit
model.)
1
3
button to
26-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm404mut-eRav-sm454mut-eRav-sm564mut-e