Diagnosis display
Abnormality/Protection control
F41
PFC control
F42
Outdoor heat exchanger temperature
sensor abnormality
F43
Outdoor defrost sensor abnormality
F45
Indoor water outlet temperature sensor
abnormality
F46
Outdoor Current Transformer open
circuit
F48
Outdoor EVA outlet temperature sensor
abnormality
F49
Outdoor bypass outlet temperature
sensor abnormality
F95
Cooling high pressure overload
protection
Abnormality judgement
4 times occurrence within 10
minutes
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
—
Continue for 5 sec.
Continue for 5 sec.
—
105
Primary location to verify
Voltage at PFC
Outdoor heat exchanger temperature
sensor (defective or disconnected)
Outdoor defrost sensor (defective or
disconnected)
Water outlet temperature sensor
(defective or disconnected)
Insufficient refrigerant
Outdoor PCB
Compressor low
Outdoor EVA outlet temperature sensor
(defective or disconnected)
Outdoor bypass outlet temperature
sensor (defective or disconnected)
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB